2002-03-26 00:00:00 | ****************** UNSAT ************** |
| |
| 1)NOTE: PLEASE CLARIFY LIGHTING FOR |
| FOOD STORAGE M-20 ON PAGE E-204. |
| |
| 2)NOTE: PLEASE NOTE THAT ALL CONTINUOUS |
| LOADS (LIGHTING) ETC ARE TO BE FIGURED |
| AND SHOWN AT 125%. 215-2/215-3 /230-42.. |
| .... |
| |
| 3)NOTE: PLEASE CLARIFY PANEL SCHEDULE |
| FOR EP4P2. SHOWS SF 1P- SF 6P? PLEASE |
| CLARIFY WHAT THESE LOADS ARE? |
| |
| 4)NOTE: PLEASE CLARIFY GROUPING OF MAINS |
| FOR EMERGENCY POWER. PLEASE NOTE MAIN |
| ELECTRICAL COMING FROM ORIG BLDG AND |
| GENERATOR POWER COMING FROM NEW BLDG |
| OUTSIDE AND UP A LEVEL. PLEASE SEE |
| FIRE PLAN REVIEW COMMENTS FOR THIS. |
| PLEASE NOTE CONCERNS OVER SHUTTING MAIN |
| OFF AND HAVINGGENERATOR START UP AND |
| STILL FEEDING POWER INTO NEW BLDG. |
| PLEASE NOTE FIREDEPT CONCERNS OVER |
| THE DISTANCE OF TRAVEL FOR SHUTTING OF |
| EM POWER IN 2-LEVEL GARAGE, THEN MCB |
| ON THE INSIDE OF GENERATOR, (IF OUTSIDE) |
| PLEASE SEE 230-72 FOR GROUPING OF MAINS, |
| AND 230-76/230-79 FOR RATING OF MAINS |
| FOR ELEC POWER. |
| |
| 5)NOTE: PLEASE SHOW LOAD CALCULATIONS |
| FOR ADDING NEW SERVICE LOAD TO EXISTING |
| SERVICE. |
| |
| 6)NOTE: PLEASE SUBMIT ALL PANEL SCHEDULE |
| S, SCDP2? PLEASE CHECK FOR ANY OTHERS. |
| |
| 7)NOTE: PLEASE CLARIFY GROUNDING ATTACH- |
| MENT FOR TRANSFORMERS.250-30 |
| |
| PLEASE SEE FIRE REVIEW COMMENTS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE NAY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |