Plan Review Notes
Plan Review Notes For Permit 02030439
Permit Number 02030439
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-29 00:00:00 
  
  
  
 DENIED
 REFERENCE: FBC-2001 POOL CODE
  
 1) GENERAL NOTES #14 PER FBC-2001 SEC
 4.24.2.6 DESIGN PER THIS SEC NOT WPB
 SWIMMING CODE.
 2) POOL DATA & EQUIPMENT - DESIGN FBC
 4.24.2.6 NOT SEC 104.1 2001 EDT.
 3) SEC 4.24.2.6.6.2 PROVIDE MANUF. SHEET
 FOR APPROVAL ON VAC LOC FOR VACUUM LINE.
 (IF HAYWARD W400AWHP STATE ON PLANS)
 4) SEC 4.24.2.7.2 PROVIDE MOUNTING DE-
 TAIL FOR EQUIPMENT. SLAB TO BE NOMINAL
 4" SLAB, (TO BE SHOWN ON DETAIL).
 5) SEC 4.24.2.9 WATER SUPPLY - UTILITY
 ORD. 2853-95 BACKFLOW REQUIRED ON WATER
 SERVICE. (STATE ON PLANS)
 6) SEC 4.24.2.12 PRESSURE TEST - NO AIR
 TEST ALLOWED FOR PVC. (STATE ON PLANS)
 7) SEC 4.24.13.2 JOINTS AND CONNECTIONS,
 PURPLE CLEANER REQUIRED FOR PVC PER
 FBC-2001 PLUMBING SEC 605.21 (STATE ON
 PLANS)
 8) FOR FUTURE INFORMATION - WHEN HEATER
 WILL BE USED SEE SECTIONS 4.24.2.6.4,
 SUBMIT MANUF. RECOMMENDATIONS, AND SEC
 4.24.2.14.2 WATER RETENTION, SHOW HOW
 WATER WILL BE RETAINED, AND SECION
 4.24.2.14.4 CONNEDTIONS FOR HEATER SHALL
 BE BY UNIONS OR FLANGES.(STATE ON PLANS)
  
  
 REVIEW BY KEN STEVENS