Plan Review Notes For Permit 02030183 |
Permit Number |
02030183 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-05-25 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 11 | | FBC-2001 PLUMBING | | | | 1) FROM PREVIOUS REVIEW, SHOWER STALL, | | SECTIONS 4.21.3, 4.21.5, 4.21.6, (60" | | MINIMUM - 59" SHOWN), & 4.21.7 HAVE NOT | | BEEN ADDRESSED. | | 2) FROM PREVIOUS REVIEW, SHTS P2.1 AND | | P5.1 STILL SHOW FLOOR DRAINS AT WATER | | HEATER. PLEASE CHANGE PLANS TO SHOW A | | FLOOR SINK FOR INDIRECT WASTE. | | 3) WHEN SUBMITTING PLANS PLEASE REMOVE | | ALL SHEETS THAT HAVE BEEN REVISED AND | | INSERT NEW SHEET. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|