2002-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) FROM PREVIOUS REVIEW, SHOWER STALL,
 SECTIONS 4.21.3, 4.21.5, 4.21.6, (60"
 MINIMUM - 59" SHOWN), & 4.21.7 HAVE NOT
 BEEN ADDRESSED.
 2) FROM PREVIOUS REVIEW, SHTS P2.1 AND
 P5.1 STILL SHOW FLOOR DRAINS AT WATER
 HEATER. PLEASE CHANGE PLANS TO SHOW A
 FLOOR SINK FOR INDIRECT WASTE.
 3) WHEN SUBMITTING PLANS PLEASE REMOVE
 ALL SHEETS THAT HAVE BEEN REVISED AND
 INSERT NEW SHEET.
  