Plan Review Notes For Permit 02030183 |
Permit Number |
02030183 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-04-04 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FACBC-97 | | | | 1) SHT PO.1 PLUMBING NOTES #13, REMOVE | | ALL REFERENCES TO AIR CHAMBERS. AIR | | CHAMBERS ARE NOT APPROVED IN FBC-2001 | | 2) SHOWER STALL ROOM NOT WIDE ENOUGH. | | SEE SECTIONS 4.21, 4.21.2, 4.21.3, | | 4.21.4, 4.21.5, 4.21.6 AND 4.21.7. | | 3) SUBMIT DETAIL FOR SHOWER STALL. SEE | | FIGS 35(A) & 35(B). COMPLY WITH FACBC | | SECTIONS 4.23,4.23.2, & 4.23.3. | | 4) WATER HEATER. PROVIDE DETAIL FOR | | RELIEF OUTLET WASTE. IF DISCHARGE IS BE- | | ING DRAINED INTO FLOOR DRAIN, ALL IN- | | DIRECT WASTE SHALL BE DRAINED TO A FLOOR | | SINK. PLEASE CLAIRFY. FBC-2001 SECS | | 504.7 & 504.7.1 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|