2002-04-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FACBC-97
  
 1) SHT PO.1 PLUMBING NOTES #13, REMOVE
 ALL REFERENCES TO AIR CHAMBERS. AIR
 CHAMBERS ARE NOT APPROVED IN FBC-2001
 2) SHOWER STALL ROOM NOT WIDE ENOUGH.
 SEE SECTIONS 4.21, 4.21.2, 4.21.3,
 4.21.4, 4.21.5, 4.21.6 AND 4.21.7.
 3) SUBMIT DETAIL FOR SHOWER STALL. SEE
 FIGS 35(A) & 35(B). COMPLY WITH FACBC
 SECTIONS 4.23,4.23.2, & 4.23.3.
 4) WATER HEATER. PROVIDE DETAIL FOR
 RELIEF OUTLET WASTE. IF DISCHARGE IS BE-
 ING DRAINED INTO FLOOR DRAIN, ALL IN-
 DIRECT WASTE SHALL BE DRAINED TO A FLOOR
 SINK. PLEASE CLAIRFY. FBC-2001 SECS
 504.7 & 504.7.1
  
 REVIEW BY KEN STEVENS