2002-05-06 00:00:00 | DENIED |
| REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| |
| A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| FORMATION REQUIRED FOR PLAN REVIEW |
| 1) COMPLY WITH FBC-2001 SEC 424.2 |
| PRIVATE SWIMMING POOLS. GENERAL NOTES |
| STATES 424.A |
| 2) FBC-2001 SEC 424.2.6.1 ENGINEERING |
| DESIGN, CONSTRUCTION AND WORKMANSHIP. |
| ANSI/NSPI-4 92. AND NSPI-5 |
| 3) FBC-2001 SEC 424.2.6.3 WATER VELOCITY |
| NOT TO EXCEED 10FT/SEC. (ADD TO NOTES) |
| 4) FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| NUMBER AND MANUF INFO FOR VAC LOCK. |
| (GIVE DETAIL OR ADD NOTE) |
| 5) FBC-2001424.2.6.6.5 WHERE PROVIDED, |
| THE VACUUM OR PRESSURE CLEANER FITTING |
| SHALL BE LOCATED AT LEAST 6" AND NOT |
| GREATER THAN 12" BELOW THE MINIMUM OPER- |
| ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| THE SKIMMER. |
| 6) FBC-2001 424.2.7.2 PUMPS AND EQUIP- |
| MENT SHALL BE MOUNTED ON A SUBSTANTIAL |
| BASE IN A MANNER THAT WILL ELIMINATE |
| STRAIN ON PIPING. SLAB SHALL BE A NOMIN- |
| AL 4" THICK. (DETAIL) |
| 7) FBC-2001 424.2.9 WATER SUPPLY, LOCAL |
| ORD. #2853-95, BACKFLOW REQUIRED ON |
| WATER SERVICE. (ADD TO NOTES) |
| 8) FBC-2001 424.2.12.1 PRESSURE TESTS. |
| PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| TEST SHALL BE APPROVED FOR PVC PIPE AND |
| FITTINGS. (ADD TO NOTES) |
| 9) FBC-2001 424.2.13.2JOINTS AND CON- |
| NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| NOTES) |
| 10) PLEASE NOTE THAT ALL SHEETS THAT ARE |
| SIGNED AND SEALED SHALL HAVE A TITLE |
| BLOCK INDICATING THEIR NAME, ADDRESS, & |
| NUMBER. |
| 11) PLEASE NOTE THAT GENERAL NOTE SHEET |
| IS NOT CLEAR AND READABLE. ALSO IT HAS |
| THE TITLE BLOCK AND SIGNATURE OF ANOTHER |
| ENGINEER. |
| 12) PLEASE NOTE THAT THERE ARE LOOSE |
| PAGES THAT WERE SUBMITTED. PLEASE SUB- |
| MIT 2 SETS OF POOL PLANS WITH ALL SHEETS |
| FOR REVIEW. |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |