Plan Review Notes For Permit 02030156 |
Permit Number |
02030156 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-03-10 00:00:00 | PLUMBING PLAN REVIEW,FBC 2001, DENIED. | | (1A)GENERAL NOTES #1 CURRENT CODE IN USE | | FBC 2001 SEC 424.2 PRIVATE SWIMMING POOL | | (1B) SEC 424.2.6 ENGINEERING DESIGN, | | PROVIDE A COPY OF CONTRACT. | | (2) SEC 424.2.6.3 WATER VELOCITY,NOT TO | | EXCEED 10FT/SEC. | | (3) SEC 424.2.6.6.2 SUCTION INLETS, | | PROVIDE CUT SHT ON TYPE OF COVER THAT | | HAS BEEN TESTED AND ACCEPTED. | | (4) SEC 424.2.6.6.5 CLEANER FITTING, | | SHOW LOCATION. | | (5) SEC 424.2.7.2 MOUNTING AND ANCHORING | | SWIMMING POOL EUIPMENT. | | (6) SEC 424.2.9 WATER SUPPLY, LOCAL ORD. | | #2853-95,BACKFLOW PREVENTER REQUIRED ON | | WATER SERVICE. | | (7) SEC 424.13.2,JOINTS AND CONNECTIONS | | FBC-2001 PLBG.SEC 605.21 PURPLE PRIMER | | REQUIRED ON PVC PIPING. | | (8) FL BUIILDING CODE, 2001 SEC 104.2.2 | | DESIGN PROFESSIONAL, BLOCK STAMP IS | | REQUIRED WITH ENGINEERS SEAL. | | END OF COMMENTS PAUL SCHMITZ | | QUESTIONS561-659-8096X8233 |
|