2002-04-10 00:00:00BUILDING PLAN REVIEW
 PERMIT# 02030113
 9434 LANTERN BAY CI
 CONT:ENGLE HOMES
 TEL: 968-5671
  
 FL BLDG CODE= 2001 FLORIDA BUILDING CODE
  
 1)- PLANS SUBMITTED AFTER FEBRUARY 28/
 2002 ARE TO BE DESIGNED BY THE 2001
 FLORIDA CODE.
 2)- FL BLDG 1606.1.7 INFORMATION ON
 DRAWINGS RELATED TO WIND SHALL BE ON THE
 CONSTRUCTION DRAWINGS, AND DESIGNED TO
 THE 2001 FL BLDG CODE.
 3)- FL BLDG 1909.3 (EXCEPTION #2 )
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4 X W1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO UPPER
 1/3RD OF THE SLAB SHALL BE SUPPORTED BY
 APPROVED MATERIALS OR SUPPORTS AT SPAC-
 ING NOT TO EXCEED 3 FT OR IN ACCORDANCE
 EITH MANUFACTURER'S SPEC.
 4)- ANCHOR SCHEDULE:
 B TYPE ANCHOR 1383 LBS UPLIFT. THE
 SIMPSON HETAL CONNECTION WITH (15)#10D
 NAILS WITH 112LBS SHEAR= 1680 OK.WHEN
 THE SAME 112 LBS SHEAR IS APPLIED TO
 (5)#10D= 560 LBS NOT THE 1383 REQUIRED?
 IT IS NOT CLEAR BUT IF THE TA & TAR
 COMBINED WITH (10) 10D@112=1120 LBS,
 STILL SHORT THE 1383.
 5) TRUSS ENGINEERING IS TO BE DESIGNED
 UNDER THE 140 MPH WIND AS OF 4/1/02.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412