2002-04-19 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT A LOCK OUT
 DEVICE SHOWN FOR WATER HEATER IS NOT
 PERMANENT. PLEASE NOTE THAT ANY WATER
 HEATER NOT WITHIN SIGHT OF PANEL REQ`S
 ADISCONNECT. 424-19
  
 2)NOTE: PLEASE NOTE MISSING SD`S INSIDE
 BEDROOMS. NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 4)) NOTE: PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372