2002-05-06 00:00:00PROVISO:
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH
 NOTIFICATION AS PER 2001 FBC(M) 606.2.1
 & NFPA 90A 4-4.4.3.
  
 AIR BALANCE REQUIRED - .001 WC OR LESS
 ACROSS CLOSED DOORS AS PER 2001 FBC(M)
 601.4.
  