Plan Review Notes For Permit 02022325 |
Permit Number |
02022325 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-03-27 00:00:00 | A) PLEASE PROVIDE MORE DETAILS ON | | SUSPENDED CLOUDS. | | B) PLEASE INDICATE EXIT PATHS IN | | VEHICLE SHOWROOM AREA. | | C) INTERIOR FINISH CLASSIFICATION | | INFORMATION REQUIRED ON WALLS AND | | CEILINGS. | | D) PLEASE INDICATE FIRE RATING OF | | EXISTING WALL BETWEEN SERVICE AND | | OFFICE AREAS. | | E) BUILDING ADDRESS REQUIRED ON | | BUILDING. | | F) PLEASE PROVIDE MORE DETAILS ON | | POLYURETHANE FOAM ROOFING. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|