Plan Review Notes
Plan Review Notes For Permit 02022303
Permit Number 02022303
Review Stop FS
Sequence Number 1
Notes
Date Text
2002-03-01 00:00:00A) THE FIRE DEPARTMENT CONNECTION
 MUST CONTAIN A CHECK VALVE.
 B) ANY NEW PIPING MUST BE TESTED AT
 200 LBS. FOR TWO HOURS.
 C) THE RELOCATED FIRE DEPARTMENT
 CONNECTION MUST HAVE 7' 6" CLEARANCE TO
 THE FRONT AND SIDES OF IT.
 D) THE PLANS INDICATES AN 1 2/2 EXISTING
 CONNECTION BUT IT IS BELIEVED THAT 2
 1/2 INCH CONNECTION EXISTS.
 E) CONNECTION MUST BE POINTED IN THE
 RIGHT DIRECTION SO THE HOSE WILL NOT
 KINK.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497