2002-03-28 00:00:00 | A) STORAGE AREAS TO BE AT LEAST ONE HOUR | | FIRE RATED AND BE EQUIPPED WITH AT | | LEAST 45 MINUTE FIRE DOORS AND BE | | EQUIPPED WITH SELF-CLOSING DEVICES SINCE | | NO FIRE SPRINKLER SYSTEM IS PLANNED. | | B) SINGLE EXIT FROM SECOND FLOOR AS | | SHOWN CANNOT BE APPROVED. PLEASE SEE | | NFPA 101, 2000 EDITION, SECTION 38.2.4.2 | | C) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | D) PLEASE PROVIDE DETAILS ON EXISTING | | STAIR. PLEASE INDICATE RISE, RUN, | | AND TREAD DEPTH. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|