Plan Review Notes For Permit 02022274 |
Permit Number |
02022274 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-03-27 00:00:00 | *************** UNSAT ****************** | | | | 1)NOTE: PLEASE SUBMIT INFORMATION FOR | | EXISTING SERVICE AND SIZE. PLEASE SUBMIT | | A LOAD CALCAULTION FOR USE AS COMMERCIAL | | OFFICE. 215-5/220-3/220-10/220-11/-13,, | | | | 2)NOTE: PLEASE SHOW ALL NEW CIRCUITING | | ON PLANS AND CORRELATE WITH SUBMITTED | | PANEL SCHEDULE. | | | | 3)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | LOADS ARE TO SHOWN AND FIGURED AT 125% | | 215-2,3. 230-42 ETC. | | | | 4)NOTE: PLEASE SHOW ALL EXISTING ELECTR- | | ICAL. NEED TO VERIFY LIGHTING. | | PLEASE SHOW LOCATION OF ELECTRICAL | | SERVICE/PANEL. | | | | 5)NOTE: PLEASE NOTE POSSIBLE MISSING | | EMLT AND EXIT LTS. PLEASE SEE FIRE | | REVIEW COMMENTS. | | | | 6)NOTE: PLEASE NOTE THAT PERMIT | | APPLICATION HAS A LISTED VALUE OF $2400, | | PLEASE NOTE THAT VALUE IS TO INCLUDE | | ALL LABOR AND MATERIALS. | | PLEASE NOTE VALUE WILL NEED TO BE | | ADJUSTED.ADMINISTRATIVE CODE 104.6.5. | | | | PLEASE SEE OTHER COMMENTYS FROM OTHER | | REVIEWERS. PLEASE SUBMIT THE ABOVE | | INFORMATION FOR REVIEW. IF THERE ARE | | ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|