Plan Review Notes
Plan Review Notes For Permit 02022274
Permit Number 02022274
Review Stop B
Sequence Number 1
Notes
Date Text
2002-03-29 00:00:00PROVIDE DETAILS FOR HANDICAP
 ACCESSIBILITY TO THE SITE AND TO THE
 PRIMARY USE AREAS OF THE STRUCTURE.THE
 RAMP SHOWN DOES NOT APPEAR TO COMPLY
 WITH SECTION 4.8 OF THE FACBC INCLUDING
 LOCATION.SEE FACBC 4.1.6 (I) RE:
 RESIDENTIAL CONVERSION.
  
 SHOW THE DIMENSIONS OF ITEMS SUCH AS
 THEDOORS BEING REPLACED, STAIR WIDTH,
 RISE RUN RATIO, AND OTHER PERTINENT
 ITEMS.
  
 THERE APPEARS TO BE TYPOS IN SECTION
 1/A2.0 AT THE HANDRAILS.
  
 THE EGRESS DOORS FROM THE BUILDING MUST
 HAVE LEVEL LANDINGS.SEE SBC 1012.1.3.
  
 SHOW THE SPECIFIC FIRE RATING FOR THE
 DOORS ENCLOSING THE STAIRS.SEE SBC
 TABLE 705.1.2.
  
 THE CONVERSION FROM RESIDENTIAL TO
 BUSINESS MAY BE SUBJECT TO IMPACT FEES
 COLLECTED BY THE COUNTY FOR THE CITY.
 THE PERMIT PLANS MUST BE STAMPED BY
 THAT OFFICEAND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 233-5025 FOR MORE
 INFORMATION.
  
 PROVIDE DETAILED PLANS OR A DESCRIPTIVE
 WRITTEN NARRATIVE OF THE CONCRETE WORK
 TO BE INCLUDED WITH THE PERMIT
 APPLICATION.SEE SBC 104.2
  
 THE DECLARED $2400 PERMIT VALUATION IS
 TOO LOW FOR THIS SCOPE OF WORK.
 PROVIDE A COPY OF THE SIGNED CONTRACT
 AND A DETAILED TAKEOFF INCLUDING
 EXTENSIONS.