Plan Review Notes
Plan Review Notes For Permit 02022248
Permit Number 02022248
Review Stop P
Sequence Number 8
Notes
Date Text
2002-08-31 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
  
 1) SHT A2.0 TOILET ROOM NEAR OFFICE AND
 DANCE ROOM DOES NOT MEET CODE PER SEC
 4.22
 2) SHT P-1 RELIEF VENTS REQUIRED ON ALL
 CONDENSATE LINES AS THEY EXIT BLDG.
 3) SHT P-1 BACKFLOW PREVENTOR REQUIRED
 ON WATER SERVICE LINE TO WET PLAY AREA.
 4) SHT P-3 DISHWASHER SHALL DRAIN INTO
 THE SANITARY DRAIN NOT GREASE SYSTEM PER
 UTILITY ORD.
 5) GAS PERMIT REQUIRED. FOLLOWING INFOR-
 MATION REQUIRED AT TIME OF GAS PERMIT
 APPLICATION.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER THE STANDARD GAS
 CODE SECS. 402.4 THRU 402.4.4.7.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER THE STANDARD GAS CODE SECS
 602 THRU 612.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 6) SHT P-3 GAS RISER - UNION REQUIRED
 BETWEEN THE MANUAL SHUT OFF VALVE AND
 THE AUTOMATIC SHUT OFF VALVE.
  
 REVIEW BY KEN STEVENS