2002-08-31 00:00:00 | DENIED |
| REFERENCE: SPC-94 - FACBC-97 - SGC-97 |
| |
| 1) SHT A2.0 TOILET ROOM NEAR OFFICE AND |
| DANCE ROOM DOES NOT MEET CODE PER SEC |
| 4.22 |
| 2) SHT P-1 RELIEF VENTS REQUIRED ON ALL |
| CONDENSATE LINES AS THEY EXIT BLDG. |
| 3) SHT P-1 BACKFLOW PREVENTOR REQUIRED |
| ON WATER SERVICE LINE TO WET PLAY AREA. |
| 4) SHT P-3 DISHWASHER SHALL DRAIN INTO |
| THE SANITARY DRAIN NOT GREASE SYSTEM PER |
| UTILITY ORD. |
| 5) GAS PERMIT REQUIRED. FOLLOWING INFOR- |
| MATION REQUIRED AT TIME OF GAS PERMIT |
| APPLICATION. |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER STANDARD |
| GAS CODE. |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| 3. TYPE OF GAS, (LP OR NATURAL) |
| 6. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER THE STANDARD GAS |
| CODE SECS. 402.4 THRU 402.4.4.7. |
| 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER STANDARD GAS CODE SEC. 305.2. IF |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| 8. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER THE STANDARD GAS CODE SECS |
| 602 THRU 612. |
| 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| STANDARD GAS CODE SEC. 402. |
| 10. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| 11. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| 12. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| 6) SHT P-3 GAS RISER - UNION REQUIRED |
| BETWEEN THE MANUAL SHUT OFF VALVE AND |
| THE AUTOMATIC SHUT OFF VALVE. |
| |