2002-05-02 00:00:00 | DENIED |
| REFERENCE: SPC-94 - SGC-97 - FACBC-97 |
| |
| 1) PLANS SHALL BE ROUTED TO THE PALM |
| BEACH COUNTY HEALTH UNIT, DIVISION OF |
| ENVIRONMENTAL HEALTH, 901 EVERNIA STREET |
| WPB FLA 33401. 3RD NOTICE |
| 2) SHT P-2, SANT RISER DIAG., JANITOR |
| MOP SINK SHALL BE ON GREASE LINE, BUT |
| THE MEZZININE FLOOR DRAIN SHALL BE ON |
| THE SANITARY SYSTEM. |
| 3) SHT A2.0 SHOWER BATH BY DANCE CLASS |
| SHALL BE ACCESSIBLE PER FACBC SEC 4.1.3 |
| (11). PLEASE SHOW 5' TURNING RADIUS, |
| CLEAR FLOOR SPACE, W/C 1'6" OFF WALL, |
| HEIGHT FOR LAV., DOOR SHALL NOT OPEN IN- |
| TO CLEAR FLOOR SPACE OF LAV. |
| 4) SHT A2.3 SECONDARY DRAIN (SCUPPER) |
| MISSING FOR ROOF ABOVE MEN'S REST ROOM. |
| 5) SHT FS-1.1 EQUIP SCHED. #10 WATER |
| FILTER SHALL BE NSF APPROVED. SUBMIT |
| MANUFACTURE INFORMATION. (FS SHEETS NOT |
| FOUND) |
| 6) SHT FS-1.1 EQUIP SCHED. #29 NO SANT. |
| OR WATER SHOWN FOR THIS EQUIP. |
| 7) SHT FS-1.2 MECH NOTES #6 IS THERE A |
| WASH DOWN FOR HOOD? |
| 8) SHT P-1 GREASE TRAP, RODNEY COMPO NOT |
| CONTACTED TO SIZE GREASE TRAP. CALLED |
| HIM MYSELF AND HE SAID HE WOULD CONTACT |
| ARCHITECT OR ENGINEER. |
| 9) SHT P-2 WATER RISER, 1" COLD OUT OF |
| WOMEN'S ROOM "TO PLAY AREA" BUT SHT P-1 |
| SHOWS IT SUPPLING A DRINKING FOUNTAIN. |
| PLEASE CLAIRFY. ALSO A SHUT OFF VALVE IS |
| REQUIRED FOR THIS LINE. |
| 10) ALL GAS FOR KITCHEN TO BE ON SEPAR- |
| ATE PERMIT. PLANS SHALL BE SUBMITTED |
| WITH PERMIT APPLICATION. |
| 11) SHT L2 WATER PLAY BY VORTEX, PUMP |
| VAULT (FOR WATER PLAY) & ENCLOSURE BY |
| VORTEX. - SUBMIT MANUFACTURE SHEETS AND |
| INFORMATION WITH LISTED APPROVAL. SHOW |
| DETAILS OF SYSTEM. SUBMIT INFORMATION TO |
| HEALTH DEPT. FOR APPROVAL BEFORE RESUB- |
| MITTING TO CITY FOR REVIEW. 2ND NOTICE, |
| THESE SHEETS NOT RESUBMITTED. |
| 12) PLANS ARE NOT COMPLETE, PLEASE IN- |
| CLUDE ALL SHEETS FOR REVIEW WHEN RESUB- |
| MITTING. |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |