2002-05-03 00:00:00 | REVIEW NOTES STRUCTURAL 5/03/02 WILLIAM |
| STAPLES 561-659-8096 EXT. 8315. |
| |
| 1. STRUCTURAL INSPECTION PLAN IS A |
| FAX.NOT COMPLETELY FILLED OUT AND NOT |
| SIGNED AND SEALED. |
| |
| 2. SPECIAL INSPECTOR FORMS SUBMITTED IS |
| A FAX. AND NOT SIGNED AN SEALED AS |
| REQUIRED BY FS 553. |
| 3. SHEET S1.0 REVISE STRUCTURAL NOTE TO |
| REQUIRE TERMITE PROTECTION OF SOIL. |
| 4.SHEET S-3.1 DETAILS A&B PROVIDE STRUC |
| TURAL CONNECTION DETAIL FOR TRUSS TO |
| BEAMS. |
| 5. SHEET S-4.0 |
| SECTION A PROVIDE FLASHING DETAIL FOR |
| ROOF TO WALL CONNECTION. |
| SECTION B PROVIDE FLASHING DETAIL FOR |
| METAL DECK AND TRUSS TO BEAM CONNECTION. |
| |
| SECTION C PROVIDE DETAIL FOR WOOD ROOF |
| SHEATING CONNECTION AND FLASHING TO |
| BLOCK WALL. PROVIDE FLASHING DETAIL FOR |
| STEEL DECK TO BLOCK WALL AT BOTH ENDS. |
| PROVIDE CONNECTION DETAIL FOR STEEL |
| TRUSSES TO BEAMS. |
| 6. SHEET S-5.0 |
| SECTION D INDICATE CONNECTION DETAIL FOR |
| ROOF SHEATING TO THE WALL FOR WOOD AND |
| STEEL DECKING, PROVIDE FLASHING DETAILS. |
| SECTIONS E, F AND G INDICATE THE |
| CONNECTOR TO BE USED FOR TRUSS TO BEAM |
| CONNECTION. |
| 7. PROVIDE THE FOLLOWING: |
| A. DESIGN LOADS FOR ALL WOOD AND STEEL |
| TRUSSES. |
| B. DESIGN PRESSURES FOR ALL OPENINGS, |
| DOOORS AND WINDOWS, PROVIDE ELEVATIONS |
| INDICATING DESIGN PRESSURES. |
| C. PROVIDE STRUCTURAL INFORMATION ON |
| LADDERS TO THREE MEZZANINE'S. |
| D. SUBMIT STRUCTURAL CALCULATIONS. |
| E. PROVIDE STRUCTURAL DESIGN FOR METAL |
| AND BUILT UP ROOF SYSTEMS. |
| 8. SEE REVIEW #1 FOR ADDITIONAL ITEMS |
| NEEDING CLARIFICATION, FOR ITEMS NOT |
| DUPLICATED TO REDUCE CONFUSION. |
| 9. REVISE PLUMBING DRAWINGS IN |
| COMFORMITY WITH CUT SHEET SECTION C ON |
| 6.3 DATED 4/26/02. |