Plan Review Notes
Plan Review Notes For Permit 02022248
Permit Number 02022248
Review Stop P
Sequence Number 1
Notes
Date Text
2002-04-01 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
  
 1) PLEASE ROUTE PLANS PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 HEALTH 901 EVERNIA STREET FOR PLAN RE-
 VIEW PRIOR TO RESUBMITTING.
 2) PROVIDE CALCULATIONS FOR MINIMUM FAC-
 ILITIES PER TABLE 407 AND SEC 407.1.3
 3) SHT A2.3PROVIDE CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SEC 1108 & 1109. ADD AREAS FROM ROOFS
 DRAINING ON TO ROOFS AND 1/2 OF AREA OF
 ALL VERTICAL WALLS.
 4) SUBMIT A STORM RISER DIAGRAM. SHOW
 ALL PIPE SIZES AND SHOW AREA DRAINED FOR
 EACH DRAIN.
 5) SHT A2.3 ROOF ABOVE COMPUTER ROOM/
 GAME ROOM, NO SECONDARY DRAIN SHOWN.
 6) SHT A6.3 DETAIL #1 W/C TO BE 1'6" TO
 CENTERLINE OFF WALL - SHOW ON DETAIL
 7) SHT A6.3 DETAIL #2 W/C TO BE 1'6" TO
 CENTERLINE OFF WALL - SHOW ON DETAIL
 8) SHT A6.3 DETAIL #3 ROLL IN SHOWER
 SHALL COMPLY WITH FIG 57 AND SECTION
 4.21. SHOW DETAILS FOR CONTROL HEIGHT,
 SEAT PLACEMENT (ADJACENT TO CONTROLS),
 GRAB BARS ECT.
 9) SHT FS-1.1 EQUIP SCHED. #10 WATER
 FILTER SHALL BE NSF APPROVED. SUBMIT
 MANUFACTURE INFORMATION.
 10 SHT FS-1.1 EQUIP SCHED. #29 NO SANT.
 OR WATER SHOWN FOR THIS EQUIP.
 11) SHT FS-1.2 MECH NOTES #6 IS THERE A
 WASH DOWN FOR HOOD?
 12) SHT P-1 GREASE TRAP, CONTACT RODNEY
 COMPO ENVIRONMENTAL COMPLIANCE FOR SIZE-
 ING OF GREASE TRAP. WASTE ORD #2938-96
 (561) 837-4074.
 13) SHTS P-1/P-2 RPZ BACKFLOW REQUIRED
 ON WATER SERVICE.
 14) SHT P-2 WATER RISER - VALVE REQUIRED
 FOR 3/4" HOT TO 3 COMP. SINK IN KITCHEN.
 15) SHT P-2 WATER RISER - W/C'S IN WOMEN
 ROOM FED BY HOT WATER/HOT & COLD TO
 DOUBLE COMP SINK REVERSED.
 16) SHT P-2 WATER RISER - 1" COLD OUT OF
 WOMENS ROOM "TO PLAY AREA" BUT SHT P-1
 SHOWS IT SUPPLYING A DRINKING FOUNTAIN.
 PLEASE CLAIRFY. ALSO A SHUT OFF VALVE IS
 REQUIRED FOR THIS LINE.
 17) SHT P-2 WATER RISER - 1" COLD WATER
 TO PLAY AREA REQUIRES A SHUT OFF VALVE,
 AND A BACKFLOW PREVENTER.
 18) SHT P-2 GAS RISER, THE FOLLOWING IN-
 FORMATION IS REQUIRED FOR GAS PERMIT
 APPROVAL. SEPARATE GAS PERMIT REQUIRED.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 F). EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 19) SHT P-3 WATER HEATER DETAIL SHOWS
 RELIEF LINE & PAN DRAIN DRAINING INTO A
 FLOOR DRAIN, BUT SHT P-1 & SHT P-2 FIX-
 TURE SCHED. SHOW LINES PIPED OUTSIDE- 6"
 ABOVE GRADE. PLEASE CLAIRFY.
 20) SHT L2 WATER PLAY BY VORTEX, PUMP
 VAULT (FOR WATER PLAY) & ENCLOSURE BY
 VORTEX. - SUBMIT MANUFACTURE SHEETS AND
 INFORMATION WITH LISTED APPROVAL. SHOW
 DETAILS OF SYSTEM. SUBMIT INFORMATION TO
 HEALTH DEPT. FOR APPROVAL BEFORE RESUB-
 MITTING TO CITY FOR REVIEW.
 21) SHT P-2 SANITARY RISER DIAGRAM,
 FLOOR DRAIN IN MENS ROOM NOT SHOWN OR
 RISER DIAGRAM.
 22) SHT P-2 2 FLOOR DRAINS SHOWN ON SHT
 P-1 FLOOR PLAN AND ONLY 1 SHOWN ON RISER
 DIAGRAM. PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS