2002-04-01 00:00:00 | DENIED |
| REFERENCE: SPC-94 - FACBC-97 - SGC-97 |
| |
| 1) PLEASE ROUTE PLANS PALM BEACH COUNTY |
| HEALTH UNIT DIVISION OF ENVIRONMENTAL |
| HEALTH 901 EVERNIA STREET FOR PLAN RE- |
| VIEW PRIOR TO RESUBMITTING. |
| 2) PROVIDE CALCULATIONS FOR MINIMUM FAC- |
| ILITIES PER TABLE 407 AND SEC 407.1.3 |
| 3) SHT A2.3PROVIDE CALCULATIONS FOR |
| PRIMARY AND SECONDARY ROOF DRAINS PER |
| SEC 1108 & 1109. ADD AREAS FROM ROOFS |
| DRAINING ON TO ROOFS AND 1/2 OF AREA OF |
| ALL VERTICAL WALLS. |
| 4) SUBMIT A STORM RISER DIAGRAM. SHOW |
| ALL PIPE SIZES AND SHOW AREA DRAINED FOR |
| EACH DRAIN. |
| 5) SHT A2.3 ROOF ABOVE COMPUTER ROOM/ |
| GAME ROOM, NO SECONDARY DRAIN SHOWN. |
| 6) SHT A6.3 DETAIL #1 W/C TO BE 1'6" TO |
| CENTERLINE OFF WALL - SHOW ON DETAIL |
| 7) SHT A6.3 DETAIL #2 W/C TO BE 1'6" TO |
| CENTERLINE OFF WALL - SHOW ON DETAIL |
| 8) SHT A6.3 DETAIL #3 ROLL IN SHOWER |
| SHALL COMPLY WITH FIG 57 AND SECTION |
| 4.21. SHOW DETAILS FOR CONTROL HEIGHT, |
| SEAT PLACEMENT (ADJACENT TO CONTROLS), |
| GRAB BARS ECT. |
| 9) SHT FS-1.1 EQUIP SCHED. #10 WATER |
| FILTER SHALL BE NSF APPROVED. SUBMIT |
| MANUFACTURE INFORMATION. |
| 10 SHT FS-1.1 EQUIP SCHED. #29 NO SANT. |
| OR WATER SHOWN FOR THIS EQUIP. |
| 11) SHT FS-1.2 MECH NOTES #6 IS THERE A |
| WASH DOWN FOR HOOD? |
| 12) SHT P-1 GREASE TRAP, CONTACT RODNEY |
| COMPO ENVIRONMENTAL COMPLIANCE FOR SIZE- |
| ING OF GREASE TRAP. WASTE ORD #2938-96 |
| (561) 837-4074. |
| 13) SHTS P-1/P-2 RPZ BACKFLOW REQUIRED |
| ON WATER SERVICE. |
| 14) SHT P-2 WATER RISER - VALVE REQUIRED |
| FOR 3/4" HOT TO 3 COMP. SINK IN KITCHEN. |
| 15) SHT P-2 WATER RISER - W/C'S IN WOMEN |
| ROOM FED BY HOT WATER/HOT & COLD TO |
| DOUBLE COMP SINK REVERSED. |
| 16) SHT P-2 WATER RISER - 1" COLD OUT OF |
| WOMENS ROOM "TO PLAY AREA" BUT SHT P-1 |
| SHOWS IT SUPPLYING A DRINKING FOUNTAIN. |
| PLEASE CLAIRFY. ALSO A SHUT OFF VALVE IS |
| REQUIRED FOR THIS LINE. |
| 17) SHT P-2 WATER RISER - 1" COLD WATER |
| TO PLAY AREA REQUIRES A SHUT OFF VALVE, |
| AND A BACKFLOW PREVENTER. |
| 18) SHT P-2 GAS RISER, THE FOLLOWING IN- |
| FORMATION IS REQUIRED FOR GAS PERMIT |
| APPROVAL. SEPARATE GAS PERMIT REQUIRED. |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER STANDARD |
| GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER STANDARD GAS CODE SEC. 305.2. IF |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| STANDARD GAS CODE SEC. 402. |
| F). EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| 19) SHT P-3 WATER HEATER DETAIL SHOWS |
| RELIEF LINE & PAN DRAIN DRAINING INTO A |
| FLOOR DRAIN, BUT SHT P-1 & SHT P-2 FIX- |
| TURE SCHED. SHOW LINES PIPED OUTSIDE- 6" |
| ABOVE GRADE. PLEASE CLAIRFY. |
| 20) SHT L2 WATER PLAY BY VORTEX, PUMP |
| VAULT (FOR WATER PLAY) & ENCLOSURE BY |
| VORTEX. - SUBMIT MANUFACTURE SHEETS AND |
| INFORMATION WITH LISTED APPROVAL. SHOW |
| DETAILS OF SYSTEM. SUBMIT INFORMATION TO |
| HEALTH DEPT. FOR APPROVAL BEFORE RESUB- |
| MITTING TO CITY FOR REVIEW. |
| 21) SHT P-2 SANITARY RISER DIAGRAM, |
| FLOOR DRAIN IN MENS ROOM NOT SHOWN OR |
| RISER DIAGRAM. |
| 22) SHT P-2 2 FLOOR DRAINS SHOWN ON SHT |
| P-1 FLOOR PLAN AND ONLY 1 SHOWN ON RISER |
| DIAGRAM. PLEASE CLAIRFY. |
| |
| REVIEW BY KEN STEVENS |