Plan Review Notes
Plan Review Notes For Permit 02022248
Permit Number 02022248
Review Stop M
Sequence Number 1
Notes
Date Text
2002-03-28 00:00:00*******************DENIED***************
  
 PLAN REVIEW UNDER 1997 SMC
  
 1.FIRE DAMPERS REQUIRED AT WHERE DUCTS
 PENETRATE A WALL WITH A RATING 1 HR
 OR GREATER.INDICATE LOCATIONS OF
 ALL FIRE DAMPERS ON PLAN AS PER 1997
 SMC 610.6.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER AHSRAE 62-1989.
  
 3.INDICATE WHERE EMERGENCY DRAIN LINE
 WILL TERMINATE - AS PER 1997 SMC
 304.8.6.1, DRAIN LINE NOTE LESS THAN
 3/4" PIPE SIZE SHALL EXTEND FROM PAN
 AND TERMINATE AT A CONSPICUOUS POINT
 TO SERVE AS AN ALARM THAT PRIMARY
 DRAIN IS RESTRICTED.
  
 4.PROVIDE DETAIL FOR THE ATTACHMENT
 OF THE CONDENSER UNIT STAND TO THE
 ROOF.PLEASE NOTE AS PER COUNTWIDE
 AMENDMENTS, 18" MINIMUM BETWEEN THE
 ROOF SURFACE AND THE BOTTOM OF THE
 SUPPORT RAIL.
  
 5.PROVIDE MANUFACTURER SUBMITTAL DATA
 FOR THE KILN.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN COOLERS OR
 FREEZERS.PROVIDE MANUFACTURER
 SUBMITTAL DATA & PLANS WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.