2002-03-28 00:00:00 | *******************DENIED*************** |
| |
| PLAN REVIEW UNDER 1997 SMC |
| |
| 1.FIRE DAMPERS REQUIRED AT WHERE DUCTS |
| PENETRATE A WALL WITH A RATING 1 HR |
| OR GREATER.INDICATE LOCATIONS OF |
| ALL FIRE DAMPERS ON PLAN AS PER 1997 |
| SMC 610.6. |
| |
| 2.PROVIDE OUTSIDE AIR CALCULATIONS AS |
| PER AHSRAE 62-1989. |
| |
| 3.INDICATE WHERE EMERGENCY DRAIN LINE |
| WILL TERMINATE - AS PER 1997 SMC |
| 304.8.6.1, DRAIN LINE NOTE LESS THAN |
| 3/4" PIPE SIZE SHALL EXTEND FROM PAN |
| AND TERMINATE AT A CONSPICUOUS POINT |
| TO SERVE AS AN ALARM THAT PRIMARY |
| DRAIN IS RESTRICTED. |
| |
| 4.PROVIDE DETAIL FOR THE ATTACHMENT |
| OF THE CONDENSER UNIT STAND TO THE |
| ROOF.PLEASE NOTE AS PER COUNTWIDE |
| AMENDMENTS, 18" MINIMUM BETWEEN THE |
| ROOF SURFACE AND THE BOTTOM OF THE |
| SUPPORT RAIL. |
| |
| 5.PROVIDE MANUFACTURER SUBMITTAL DATA |
| FOR THE KILN. |
| |
| ADDITIONAL PERMITS REQUIRED FOR HOOD, |
| FIRE SUPRESSION AND WALK-IN COOLERS OR |
| FREEZERS.PROVIDE MANUFACTURER |
| SUBMITTAL DATA & PLANS WITH PERMIT |
| APPLICATION. |
| |