2002-03-26 00:00:00A) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM. THE FIRE ALARM
 SYSTEM TO BE CLASS A OR FULLY
 ADDRESSABLE. CUT SHEETS, WIRING DIAGRAM
 AND BATTERY CALCULATIONS REQUIRED.
 B) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY HOOD,DUCT, AND FIRE SUPPRESSION
 SYSTEMS PLANNED FOR USE.
 C) PLEASE PROVIDE MORE DETAILS ON
 PROPOSED KILN.
 D) OCCUPANT LOAD TO BE DETERMINED BY
 FIRE RESCUE.
 E) PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS SUBJECT TO AN OCCUPANCY LOAD OF
 100 OR MORE PERSONS.
 F) PLEASE INDENTIFY MAIN INGRESS AND
 EGRESS FOR THE BUILDING THAT IS CAPABLE
 OF PROVIDING EXITING FOR AT LEAST 50 %
 OF THE OCCUPANT LOAD FOR THE BUILDING.
 G) ANY COVERED WALKWAYS, IF COMBUSTIBLE
 OVER FOUR FEET WIDE ARE TO BE FIRE
 SPRINKLER PROTECTEDC.
 H) NO FIRE DEPARTMENT CONNECTION SHOWN
 ON FIRE SPRINKLER DRAWINGS. THIS
 CONNECTION MUST BE NO MORE THAN 150 FEET
 FROM A FIRE HYDRANT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910