2002-03-26 00:00:00 | A) SEPARATE PLANS AND PERMITS REQUIRED | | FOR FIRE ALARM SYSTEM. THE FIRE ALARM | | SYSTEM TO BE CLASS A OR FULLY | | ADDRESSABLE. CUT SHEETS, WIRING DIAGRAM | | AND BATTERY CALCULATIONS REQUIRED. | | B) SEPARATE PLANS AND PERMITS REQUIRED | | FOR ANY HOOD,DUCT, AND FIRE SUPPRESSION | | SYSTEMS PLANNED FOR USE. | | C) PLEASE PROVIDE MORE DETAILS ON | | PROPOSED KILN. | | D) OCCUPANT LOAD TO BE DETERMINED BY | | FIRE RESCUE. | | E) PANIC HARDWARE REQUIRED ON ALL EXIT | | DOORS SUBJECT TO AN OCCUPANCY LOAD OF | | 100 OR MORE PERSONS. | | F) PLEASE INDENTIFY MAIN INGRESS AND | | EGRESS FOR THE BUILDING THAT IS CAPABLE | | OF PROVIDING EXITING FOR AT LEAST 50 % | | OF THE OCCUPANT LOAD FOR THE BUILDING. | | G) ANY COVERED WALKWAYS, IF COMBUSTIBLE | | OVER FOUR FEET WIDE ARE TO BE FIRE | | SPRINKLER PROTECTEDC. | | H) NO FIRE DEPARTMENT CONNECTION SHOWN | | ON FIRE SPRINKLER DRAWINGS. THIS | | CONNECTION MUST BE NO MORE THAN 150 FEET | | FROM A FIRE HYDRANT. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|