Plan Review Notes
Plan Review Notes For Permit 02022248
Permit Number 02022248
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-20 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT THE ELECTRICAL
 SECTION IN THE SPEC BOOKS REFERENCE ALL
 THE OLD CODES. BLDG/FIRE/ELEC/ACCESS,ECT
 PLEASE CHECK FOR ALL CURRENT CODES THAT
 ARE IN AFFECT AT TIME OF APPLICATION.
 PLEASE NOTE; WE ARE UNDER "99" NEC,
 "96" NFPA-72. AND LOCAL AMENDMENTS.
  
 2)NOTE: PLEASE NOTE THAT PER ART 215
 OF CITY-WIDE ELECTRICAL AMENDMENTS.
 COLOR CODING OF 277V/480V STANDS AT
 BROWN/PURPLE/ YELLOW. PLEASE CORRECT.
  
 3)NOTE: PLEASE NOTE THAT NOTE #1 ON E-3
 SAYS MAIN RATED AT 65AIC. PLEASE NOTE
 THAT E-4 MDP IS SHOWN AT 22,000 AIC?
 PLEASE CORRELATE. 110-9/215-5
 PLEASE ALSO NOTE E-3 SHOWS 10,000 AIC
 FOR BRANCH BRKLRS.
  
 4)NOTE: PLEASE NOTE THAT NOTE 12 ON E-3
 SAYS "EQUIPMENT GROUND" PLEASE CLARIFY
 AS "GROUNDING ELECTRODE".
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 'REVIEW. PLEASE MAKE CORRECTIONS AS
 NOTED. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372