2002-04-04 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT# 02022248 |
| 345 SUMMA STREET |
| CONT: WHITING - TURNER |
| TEL: 832-4995 |
| |
| SBC= 1997 STANDARD BUILDING CODE |
| SBC*= AMENDMENTS TO THE STANDARD BUILD- |
| ING CODE |
| FL ACC= 1997 FLORIDA ACCESSIBILITY CODE |
| |
| NOTE: FLORIDA STATE STATUTE 553.80 2(B) |
| THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| TIME AFTER THE THIRD SUCH REVIEW THE |
| PLANS ARE REJECTED FOR THE SAME CODE |
| VIOLATION, A FEE OF FOUR TIMES THE |
| AMOUNT OF THE PROPORTION OF THE PERMIT |
| FEE ATTRIBUTED TO PLAN REVIEW. |
| |
| THESE PLANS ARE INCOMPLETE, NO STRUCTUR- |
| AL REFRENCES, ARCHETECT HAS NOT GIVEN |
| ANY INFORMATION TO FOOTING SIZE, COLUMN |
| OR BEAM SIZE. |
| |
| THE ARCHETECT OF RECORD DOESN'T GIVE THE |
| ANY INFORMATION AS TO HOW THE BUILDING |
| WAS DESIGNED! IMPORTANCE FACTOR,MEAN |
| ROOF HEIGTH, ETC. THESE PLAN ARE ONLY |
| A CONCEPTUAL RENDERING. |
| |
| 1)- SBC 1804.2.7.2(3) A COMPLETE SOILS |
| REPORT IS REQUIRED, 3 COPIES. |
| 2)- SBC 104.2.2* A SURVEY LESS THAN A |
| YEAR OLD. |
| 3)- SBC 1606.2.6.2COMPONENTS & CLADDING |
| THE CONTRACTOR IS TO SUPPLY THE PRODUCT |
| TESTING REPORTS FOR THE FOLLOWING ITEMS: |
| ALL GLAZED OPENINGS, WINDOWS, EXT. |
| DOORS, SKYLIGHTS & ROOFING ASSEMBLIES |
| AND STORM SHUTTERS. |
| 4) TO INDICATE THE POSITIVE & NEGATIVE |
| WIND ZONES ON THE ELEVATIONS FOR ALL |
| OPENINGS. |
| 5) MISSING TRUSS LAYOUT SHEET, INDICATE |
| THE TRUSS & GIRDER LOADS, VERTICAL, HOR- |
| IZONTAL & GRAVITY LOADS THAT ARE TO |
| BE RESISTED. |
| 6) MISSING ANCHOR SCHEDULE WITH TYPE |
| OF ANCHOR, ALLOWABLE LOADS.(TRUSSES) |
| 7) SHEET A-5 SECTION 2 & 3 ONE INDICATES |
| WOOD TRUSSES THE OTHER METAL TRUSSES. |
| WITHOUT KNOWING HOW THE ARCHETECT |
| DESIGNED THIS BUILDING WHICH IS RIGHT? |
| TYPE IV OR TYPE V BUILDING? |
| 8) SAME SECTIONS, SECTION 2 DOES NOT |
| INDICATE THE TYPE OF ROOF SHEATHING ON |
| WOOD TRUSSES, WHERE AS SECTION 3 INDICAT |
| ES METAL TRUSSES, METAL DECKING, 3" |
| INSULATION AND PLYWOOD SHEATHING, WHAT |
| TYPE OF ATTACHMENT AND WHAT FREQUENCY? |
| 9) SHEET A-5 INDICATES A VENEERED EXT. |
| WALL? TO COMPLY WITH 1403.2.6. FOR |
| ANCHORING. |
| 10) THE PLANS AARE NOT THOROUGH ENOUGH |
| TO COMPLETE A REVIEW OF THE BUILDING, |
| ALTHOUGH A FOUNDATION PERMIT IS APPLIED |
| FOR THE STRUCTURAL PLANS SHALL ALSO |
| ACCOMPANY THE ARCHETECTURAL PLANS FOR |
| DISCREPANCIES, AND VARIFICATION AS TO |
| THE ARCH. & ENGINEER HAVE THE SAME |
| CONCEPT FOR THIS PROJECT. |
| 11) SHEET A-5 DETAIL 3 INDICATES A |
| PLASTER SOFFIT AND CEILING ON AN UNDIS- |
| CLOSED FRAMING MEMBER? DETAILS, STEEL |
| STUDS, EXPANDED WIRE LATH OR ROCK LATH |
| HOW IS THE STRUCTURE SUPPORTED? |
| THE SAME DETAIL INDICATES A RAISED STUC- |
| CO BAND, IS THIS A SOLID STUCCO BAND? |
| INDICATE ATTACHMENT HI RIB / HORIZ FRAM? |
| 12) FL ACC CODE 4.33.3 BLEACHERS EXCEP- |
| TION ALLOWS FOR BLEACHER SEATING <300 TO |
| HAVE ACCESSIBLE VIEWING AREAS MAY BE |
| CLUSTERED, EQUIVALENT ACCESSIBLE VIEWING |
| POSITIONS MAY BE ON LEVELS HAVING |
| ACCESSIBLE EGRESS. SHOW COMPLIANCE. |
| 13 THE SAME COMMENTS AS THE FOUNDATION |
| PERMIT.WHAT CODE DESIGNED BY? |
| 14) THRESHOLD BUILDING, THRESHOLD INSP |
| REQUIRED, ENGINEER TO COMPRISE THRESHOLD |
| INSPECTION PLAN! |
| 15) MEET WITH DON NEELY ASSISTANT |
| BUILDING OFFICIAL. |
| 16) 3 SETS OF PLANS |
| 17) PLANS TO COUNTY IMPACT FEES |
| 18) RADON FEES DUE UNDER FOUNDATION |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561)659-8096X8412 |