2002-04-04 00:00:00BUILDING PLAN REVIEW
 PERMIT# 02022248
 345 SUMMA STREET
 CONT: WHITING - TURNER
 TEL: 832-4995
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS TO THE STANDARD BUILD-
 ING CODE
 FL ACC= 1997 FLORIDA ACCESSIBILITY CODE
  
 NOTE: FLORIDA STATE STATUTE 553.80 2(B)
 THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE
 PLANS ARE REJECTED FOR THE SAME CODE
 VIOLATION, A FEE OF FOUR TIMES THE
 AMOUNT OF THE PROPORTION OF THE PERMIT
 FEE ATTRIBUTED TO PLAN REVIEW.
  
 THESE PLANS ARE INCOMPLETE, NO STRUCTUR-
 AL REFRENCES, ARCHETECT HAS NOT GIVEN
 ANY INFORMATION TO FOOTING SIZE, COLUMN
 OR BEAM SIZE.
  
 THE ARCHETECT OF RECORD DOESN'T GIVE THE
 ANY INFORMATION AS TO HOW THE BUILDING
 WAS DESIGNED! IMPORTANCE FACTOR,MEAN
 ROOF HEIGTH, ETC. THESE PLAN ARE ONLY
 A CONCEPTUAL RENDERING.
  
 1)- SBC 1804.2.7.2(3) A COMPLETE SOILS
 REPORT IS REQUIRED, 3 COPIES.
 2)- SBC 104.2.2* A SURVEY LESS THAN A
 YEAR OLD.
 3)- SBC 1606.2.6.2COMPONENTS & CLADDING
 THE CONTRACTOR IS TO SUPPLY THE PRODUCT
 TESTING REPORTS FOR THE FOLLOWING ITEMS:
 ALL GLAZED OPENINGS, WINDOWS, EXT.
 DOORS, SKYLIGHTS & ROOFING ASSEMBLIES
 AND STORM SHUTTERS.
 4) TO INDICATE THE POSITIVE & NEGATIVE
 WIND ZONES ON THE ELEVATIONS FOR ALL
 OPENINGS.
 5) MISSING TRUSS LAYOUT SHEET, INDICATE
 THE TRUSS & GIRDER LOADS, VERTICAL, HOR-
 IZONTAL & GRAVITY LOADS THAT ARE TO
 BE RESISTED.
 6) MISSING ANCHOR SCHEDULE WITH TYPE
 OF ANCHOR, ALLOWABLE LOADS.(TRUSSES)
 7) SHEET A-5 SECTION 2 & 3 ONE INDICATES
 WOOD TRUSSES THE OTHER METAL TRUSSES.
 WITHOUT KNOWING HOW THE ARCHETECT
 DESIGNED THIS BUILDING WHICH IS RIGHT?
 TYPE IV OR TYPE V BUILDING?
 8) SAME SECTIONS, SECTION 2 DOES NOT
 INDICATE THE TYPE OF ROOF SHEATHING ON
 WOOD TRUSSES, WHERE AS SECTION 3 INDICAT
 ES METAL TRUSSES, METAL DECKING, 3"
 INSULATION AND PLYWOOD SHEATHING, WHAT
 TYPE OF ATTACHMENT AND WHAT FREQUENCY?
 9) SHEET A-5 INDICATES A VENEERED EXT.
 WALL? TO COMPLY WITH 1403.2.6. FOR
 ANCHORING.
 10) THE PLANS AARE NOT THOROUGH ENOUGH
 TO COMPLETE A REVIEW OF THE BUILDING,
 ALTHOUGH A FOUNDATION PERMIT IS APPLIED
 FOR THE STRUCTURAL PLANS SHALL ALSO
 ACCOMPANY THE ARCHETECTURAL PLANS FOR
 DISCREPANCIES, AND VARIFICATION AS TO
 THE ARCH. & ENGINEER HAVE THE SAME
 CONCEPT FOR THIS PROJECT.
 11) SHEET A-5 DETAIL 3 INDICATES A
 PLASTER SOFFIT AND CEILING ON AN UNDIS-
 CLOSED FRAMING MEMBER? DETAILS, STEEL
 STUDS, EXPANDED WIRE LATH OR ROCK LATH
 HOW IS THE STRUCTURE SUPPORTED?
 THE SAME DETAIL INDICATES A RAISED STUC-
 CO BAND, IS THIS A SOLID STUCCO BAND?
 INDICATE ATTACHMENT HI RIB / HORIZ FRAM?
 12) FL ACC CODE 4.33.3 BLEACHERS EXCEP-
 TION ALLOWS FOR BLEACHER SEATING <300 TO
 HAVE ACCESSIBLE VIEWING AREAS MAY BE
 CLUSTERED, EQUIVALENT ACCESSIBLE VIEWING
 POSITIONS MAY BE ON LEVELS HAVING
 ACCESSIBLE EGRESS. SHOW COMPLIANCE.
 13 THE SAME COMMENTS AS THE FOUNDATION
 PERMIT.WHAT CODE DESIGNED BY?
 14) THRESHOLD BUILDING, THRESHOLD INSP
 REQUIRED, ENGINEER TO COMPRISE THRESHOLD
 INSPECTION PLAN!
 15) MEET WITH DON NEELY ASSISTANT
 BUILDING OFFICIAL.
 16) 3 SETS OF PLANS
 17) PLANS TO COUNTY IMPACT FEES
 18) RADON FEES DUE UNDER FOUNDATION
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412