Date |
Text |
2003-03-18 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE NOTE THAT THERE HAVE BEEN NEW | | LOADS ADDED TO THE UNITS ON PREVIOUS | | REVISIONS WITHOUT UPDATED | | CALCULATIONS.WATER HEATERS,EQUIPMENT | | CIRCUITS AND A 30 AMP "COOLER" CIRCUIT | | WERE ADDED. | | | | PLEASE REVISE CALCULATIONS SHOWING | | ACTUAL LOADS AFTER AND PRIOR TO DEMAND | | FACTORS.REVISE THE SERVICE TO SHOW SAME. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT.8392 |
|