Plan Review Notes For Permit 02021928 |
Permit Number |
02021928 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2003-04-30 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR REVIEW | | | | PLAN SHEET 1 (PLAN/RISER/SCHED), | | INDICATES A AHU WITH CU ON THE ROOF. | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | FOR REVIEW WITH MECHANICAL PERMIT | | APPLICATION. | | | | 1.OUTSIDE AIR CALCS AS PER 2001 FBC(M) | | TABLE 403.3. | | | | 2.EXHAUST FANS FOR RESTROOMS, (MAKE, | | MODEL, CFMS).INDICATE LOCATION OF | | EXHAUST FANS. | | | | 3.PROVIDE DUCT LAYOUT. | | | | 4.SHOW COMPLIANCE WITH 2001 FBC | | 1511.7 ON THE HEIGHT FOR THE CONDENSER | | UNIT STANDS ON THE ROOF.PLEASE | | PROVIDE DETAIL. | | | | 5.EQUIPMENT LOCATED ON THE ROOF AT A | | HEIGHT EXCEEDING 16 FT SHALL HAVE A | | PERMANENT MEANS OF ACCESS. 2001 FBC(M) | | 306.5. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|