Plan Review Notes
Plan Review Notes For Permit 02021928
Permit Number 02021928
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-04 00:00:00DENIED
 REFERENCE: FACBC-97 - BUILDING CODE ??
  
 1) PLANS DO NOT SPECIFY WHICH CODE THIS
 BLDG IS DESIGNED UNDER. PLEASE INDICATE
 EITHER SPC OR FLA. BLDG CODE FOR REVIEW.
 2) SHT #1 PLEASE PROVIDE MINIMUM FACIL-
 ITIES. DRINKING FOUNTAIN - SERVICE SINK
 ECT MIGHT BE REQUIRED PER CODE.
 3) SHTS #'S 2 & 3PLEASE CALCULATE PRI-
 MARY AND SECONDARY ROOF DRAINS PER CODE.
 CONSIDER 1/2 AREA OF VERTICAL WALLS FOR
 EACH CALCULATIONS AND SHOW LOCATIONS OF
 PRIMARY AND SECONDARY DRAIN ON PLANS.
 SUBMIT STORM RISER DIAGRAMS AND INDICATE
 DOWNSPOUT/LEADER SIZE.
 4) SHT 1 WATER RISER DIAGRAM REQUIRED.
 SHOW PIPE SIZES, AND IF WATER HAMMER
 ARRESTORS ARE SHOWN LOCATION SHALL BE
 NEAR FIXTURE IN AN "EFFECTIVE RANGE" NOT
 AT TOP OF DROP.
 5) BACKFLOW REQUIRED ON WATER SERVICE.
 LOCATION TO BE APPROVED BEFORE INSTALL-
 ATION. CALL 659-8005
 6) PLUMBING CONTRACTOR TO SUPPLY VALVE,
 BACKFLOW (WATTS N36), AND ADAPTOR FOR
 IRRIGATION CONTRACTOR.
 7) SEPARATE PERMIT REQUIRED FOR IRRIGAT-
 ION. SUBMIT PLANS WITH PERMIT APPLICAT-
 ION.
  