Plan Review Notes For Permit 02021928 |
Permit Number |
02021928 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-03-04 00:00:00 | DENIED | | REFERENCE: FACBC-97 - BUILDING CODE ?? | | | | 1) PLANS DO NOT SPECIFY WHICH CODE THIS | | BLDG IS DESIGNED UNDER. PLEASE INDICATE | | EITHER SPC OR FLA. BLDG CODE FOR REVIEW. | | 2) SHT #1 PLEASE PROVIDE MINIMUM FACIL- | | ITIES. DRINKING FOUNTAIN - SERVICE SINK | | ECT MIGHT BE REQUIRED PER CODE. | | 3) SHTS #'S 2 & 3PLEASE CALCULATE PRI- | | MARY AND SECONDARY ROOF DRAINS PER CODE. | | CONSIDER 1/2 AREA OF VERTICAL WALLS FOR | | EACH CALCULATIONS AND SHOW LOCATIONS OF | | PRIMARY AND SECONDARY DRAIN ON PLANS. | | SUBMIT STORM RISER DIAGRAMS AND INDICATE | | DOWNSPOUT/LEADER SIZE. | | 4) SHT 1 WATER RISER DIAGRAM REQUIRED. | | SHOW PIPE SIZES, AND IF WATER HAMMER | | ARRESTORS ARE SHOWN LOCATION SHALL BE | | NEAR FIXTURE IN AN "EFFECTIVE RANGE" NOT | | AT TOP OF DROP. | | 5) BACKFLOW REQUIRED ON WATER SERVICE. | | LOCATION TO BE APPROVED BEFORE INSTALL- | | ATION. CALL 659-8005 | | 6) PLUMBING CONTRACTOR TO SUPPLY VALVE, | | BACKFLOW (WATTS N36), AND ADAPTOR FOR | | IRRIGATION CONTRACTOR. | | 7) SEPARATE PERMIT REQUIRED FOR IRRIGAT- | | ION. SUBMIT PLANS WITH PERMIT APPLICAT- | | ION. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|