2002-03-06 00:00:00 | FAILED : |
| 1. PLEASE SHOW LOCATIONS FOR METER AND |
| BACKFLOW PREVENTERS. |
| 2. PLEASE SHOW THE INVERT ELEVATION FOR |
| EXISTING SERVICE LATERAL AND/OR CLEAN- |
| OUT FROM MAIN. |
| 3. IT SHALL BE THE RESPONSIBILITY OF THE |
| DEVELOPER/ENGINEER/CONTRACTOR TO DESIGN |
| AND INSTALL THE NEW INVERT ELEVATION FOR |
| THE BUILDING LATERAL TO MATCH OR BE |
| HIGHER THAN THE EXISTING WHILE MAINTAIN- |
| ING THE PLUMBING CODE REQUIREMENT FOR |
| EFFLUENT PIPE FALL WITH MINIMUM OF THREE |
| FEET COVER. IF THESE REQUIREMENTS CAN |
| NOT BE MET, THE CITY MUST BE NOTIFIED |
| PRIOR TO INSTALLATION.659-8040, 659-8079 |
| 4. CIVIL PLANS MUST BE REVIEWED AND |
| APPROVED BY PUBLIC UTILITIES ENGINEERING |
| SERVICES 659-8040 EXT. 2306 M. GONZALEZ. |
| 4. CITY'S STANDARD MAY BE OBTAINED FROM |
| PUBLIC UTILITIES ENGINEERING SERVICES, |
| 659-8040, EXT.2306 M. GONZALEZ |
| 5. DUMPSTER ENCLOSURE MUST BE PER CITY'S |
| REQUIREMENT IF GARBAGE TO BE PICKED UP |
| BY THE CITY, SEE ATTACHED. |
| 6. WATER QUALITY INLET IN DUMPSTER |
| ENCLOSURE AREA IS NOT RECOMMENDED. |
| 7. DRIVEWAY APPROACHES MUST AT MIN. BE |
| PER CITY'S STANDARD, SEE ATTACHED. |
| 8. CRUSHED CONCRETE FOR THE BASE |
| CONSTRUCTION WOULD NOT BE ACCEPTABLE. |
| 9. POLLUTION PREVENTION PLANS MUST BE |
| INSTALLED IN FIELD PRIOR TO ANY EARTH |
| WORKS. NOTE TO THE G.C MUST BE ADDED. |
| IF ANY QUESTIONS PLEASE CONTACT 659-8096 |
| EXT. 8492 MOHAMMAD R. AMINI |