Plan Review Notes
Plan Review Notes For Permit 02021928
Permit Number 02021928
Review Stop ENG
Sequence Number 1
Notes
Date Text
2002-03-06 00:00:00FAILED :
 1. PLEASE SHOW LOCATIONS FOR METER AND
 BACKFLOW PREVENTERS.
 2. PLEASE SHOW THE INVERT ELEVATION FOR
 EXISTING SERVICE LATERAL AND/OR CLEAN-
 OUT FROM MAIN.
 3. IT SHALL BE THE RESPONSIBILITY OF THE
 DEVELOPER/ENGINEER/CONTRACTOR TO DESIGN
 AND INSTALL THE NEW INVERT ELEVATION FOR
 THE BUILDING LATERAL TO MATCH OR BE
 HIGHER THAN THE EXISTING WHILE MAINTAIN-
 ING THE PLUMBING CODE REQUIREMENT FOR
 EFFLUENT PIPE FALL WITH MINIMUM OF THREE
 FEET COVER. IF THESE REQUIREMENTS CAN
 NOT BE MET, THE CITY MUST BE NOTIFIED
 PRIOR TO INSTALLATION.659-8040, 659-8079
 4. CIVIL PLANS MUST BE REVIEWED AND
 APPROVED BY PUBLIC UTILITIES ENGINEERING
 SERVICES 659-8040 EXT. 2306 M. GONZALEZ.
 4. CITY'S STANDARD MAY BE OBTAINED FROM
 PUBLIC UTILITIES ENGINEERING SERVICES,
 659-8040, EXT.2306 M. GONZALEZ
 5. DUMPSTER ENCLOSURE MUST BE PER CITY'S
 REQUIREMENT IF GARBAGE TO BE PICKED UP
 BY THE CITY, SEE ATTACHED.
 6. WATER QUALITY INLET IN DUMPSTER
 ENCLOSURE AREA IS NOT RECOMMENDED.
 7. DRIVEWAY APPROACHES MUST AT MIN. BE
 PER CITY'S STANDARD, SEE ATTACHED.
 8. CRUSHED CONCRETE FOR THE BASE
 CONSTRUCTION WOULD NOT BE ACCEPTABLE.
 9. POLLUTION PREVENTION PLANS MUST BE
 INSTALLED IN FIELD PRIOR TO ANY EARTH
 WORKS. NOTE TO THE G.C MUST BE ADDED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI