2002-04-17 00:00:00 | ************* UNSAT ****************** |
| |
| 1) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210-8-A-6. |
| INCLUDES KITCHEN ISLANDS. |
| |
| 2 )NOTE: PLEASE NOTE KITCHEN COUNTER- |
| -SPACE RECEPT SPACING SHALL MEET ART; |
| 210-52C 1,2,3,4,AND 5. |
| MISSING COUNTER AND PENINSULARS. |
| |
| 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| GOING TO BUILDING STEEL AND COLD WATER |
| PER 250-50. SIZE PER 250-66 |
| |
| 4)NOTE: PLEASE NOTE THAT SD ON LOWER |
| LEVEL SHALL BE MOUNTED IN CLOSE |
| PROXIMITY TO THE STAIRWAY LEADING TO THE |
| FLOOR ABOVE. NFPA-72 2-5.2.1.3. SHOW |
| |
| 5)NOTE: PLEASE NOTE MISSING BATH GFI |
| IN LOWER BATHROOM PER 210-52D. |
| |
| 6)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| A/C EQUIPMENT. PER 210-63 AND/OR SECTION |
| 306 OF THE MECHANICAL CODE. |
| |
| 7)NOTE: PLEASE NOTE THAT AHU#3 IS NOT |
| SHOWN? PLEASE CLARIFY. COND UNIT#3 IS |
| SHOWN ,BUT NOT AHU. |
| PLEASE SHOW/CLARIFYDISC`S NOT SHOWN |
| PER 440-11. |
| |
| 8)NOTE: PLEASE NOTE THAT GARAGR OUTLET |
| IS TO BE SHOWN AS GFI/GFI PROTECTED, |
| 210-8 |
| |
| 9)NOTE: PLEASE NOTE/CLARIFY REQ`ED MEANS |
| OF EGRESS LIGHTING FOR HALL/STAIRWAY. |
| SHOWN AS "J"-BOX ONLY. PLEASE SEE OTHER |
| HALLS, HABITABLE ROOMS ANDBACK PORCH. |
| 210-70 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |