Plan Review Notes
Plan Review Notes For Permit 02021919
Permit Number 02021919
Review Stop E
Sequence Number 2
Notes
Date Text
2002-04-17 00:00:00************* UNSAT ******************
  
 1) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 2 )NOTE: PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
 MISSING COUNTER AND PENINSULARS.
  
 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. SIZE PER 250-66
  
 4)NOTE: PLEASE NOTE THAT SD ON LOWER
 LEVEL SHALL BE MOUNTED IN CLOSE
 PROXIMITY TO THE STAIRWAY LEADING TO THE
 FLOOR ABOVE. NFPA-72 2-5.2.1.3. SHOW
  
 5)NOTE: PLEASE NOTE MISSING BATH GFI
 IN LOWER BATHROOM PER 210-52D.
  
 6)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 7)NOTE: PLEASE NOTE THAT AHU#3 IS NOT
 SHOWN? PLEASE CLARIFY. COND UNIT#3 IS
 SHOWN ,BUT NOT AHU.
 PLEASE SHOW/CLARIFYDISC`S NOT SHOWN
 PER 440-11.
  
 8)NOTE: PLEASE NOTE THAT GARAGR OUTLET
 IS TO BE SHOWN AS GFI/GFI PROTECTED,
 210-8
  
 9)NOTE: PLEASE NOTE/CLARIFY REQ`ED MEANS
 OF EGRESS LIGHTING FOR HALL/STAIRWAY.
 SHOWN AS "J"-BOX ONLY. PLEASE SEE OTHER
 HALLS, HABITABLE ROOMS ANDBACK PORCH.
 210-70
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372