Plan Review Notes For Permit 02021919 |
Permit Number |
02021919 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-03-14 00:00:00 | *****************UNSAT!***************** | | PLEASE COMPLY WITH THE FOLLOWING AND | | RESUBMIT FOR REVIEW: | | | | 1} PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S) PER 210-11-C-3. | | MUST BE 20A AND #12AWG. | | | | | | 2} PLEASE SHOW ALL OUTLETS | | SERVING KITCHEN COUNTERSPACE AS GFI/GFI | | PROTECT--ED PER 210-8-A-6,AND | | 210-52(C)(1)&(C)(3) | | | | 3} SHOW DISCONNECT LOCATIONS FOR A/C | | CONDENSORS. | | | | 4} GFI'S AT CONDENSORS PER 210-63NEC & | | 309.2 MECHANICAL CODE. | | | | 5} GARAGE GFI'S PER 210-52(G) | | | | 6} SMOKE DETECTOR @ 1ST FLOOR STAIRWELL | | TO COMPLY WITH 2-5.2.1.4 NFPA-72. | | | | 7} DEN BATH GFI PER 210-52(D). | | | | 8} SMOKE DETECTOR @ 1ST FLOOR DEN BATH | | 2-5.2.1.6 NFPA-72.( 3'). | | | | 9} BED ROOM CIRCUITS TO COMPLY WITH | | 210-12 NEC. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/659-8096 EXT.8392 |
|