2002-03-14 00:00:00*****************UNSAT!*****************
 PLEASE COMPLY WITH THE FOLLOWING AND
 RESUBMIT FOR REVIEW:
  
 1} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
  
 2} PLEASE SHOW ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6,AND
 210-52(C)(1)&(C)(3)
  
 3} SHOW DISCONNECT LOCATIONS FOR A/C
 CONDENSORS.
  
 4} GFI'S AT CONDENSORS PER 210-63NEC &
 309.2 MECHANICAL CODE.
  
 5} GARAGE GFI'S PER 210-52(G)
  
 6} SMOKE DETECTOR @ 1ST FLOOR STAIRWELL
 TO COMPLY WITH 2-5.2.1.4 NFPA-72.
  
 7} DEN BATH GFI PER 210-52(D).
  
 8} SMOKE DETECTOR @ 1ST FLOOR DEN BATH
 2-5.2.1.6 NFPA-72.( 3').
  
 9} BED ROOM CIRCUITS TO COMPLY WITH
 210-12 NEC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392