Plan Review Notes For Permit 02021900 |
Permit Number |
02021900 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-05-05 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE CORRECT AND RESUBMIT FOR REVIEW. | | | | 1} THE #4 GEC IS INCORRECT FOR FOR THE | | SERVICE SHOWN.MUST BE #2 PER 250-66. | | | | 2} THE FEED FROM THE METER TO PANEL "B" | | IS INCORRECTLY SHOWN WITH A GROUND WIRE | | PARALLELING THE NEUTRAL. | | | | 3} PANEL "B" IS SHOWN AS A "MLO" PANEL. | | THIS PANEL MUST HAVE A MAIN DISCONNECT | | PER 230-71,OR HAVE A MAIN DISCONNECT | | AHEAD OF IT. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|