Plan Review Notes
Plan Review Notes For Permit 02021900
Permit Number 02021900
Review Stop E
Sequence Number 3
Notes
Date Text
2003-05-05 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE CORRECT AND RESUBMIT FOR REVIEW.
  
 1} THE #4 GEC IS INCORRECT FOR FOR THE
 SERVICE SHOWN.MUST BE #2 PER 250-66.
  
 2} THE FEED FROM THE METER TO PANEL "B"
 IS INCORRECTLY SHOWN WITH A GROUND WIRE
 PARALLELING THE NEUTRAL.
  
 3} PANEL "B" IS SHOWN AS A "MLO" PANEL.
 THIS PANEL MUST HAVE A MAIN DISCONNECT
 PER 230-71,OR HAVE A MAIN DISCONNECT
 AHEAD OF IT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718