2003-04-30 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE CORRECT THE FOLLOWING AND | | RESUBMIT FOR REVIEW. | | | | 1} THE #6 GEC IS INCORRECT FOR THE | | SERVICE SHOWN.MUST BE #2 PER 250-66. | | | | 2} THE RISER DIAGRAM SHOWS BOTH SUB | | PANELS COMING FROM PANEL "A",ONLY ONE | | LISTED ON THE THE SCHEDULE.PLEASE | | CLARIFY. | | | | 3} THE SUB FEEDERS IN PVC MUST CONTAIN | | AN EQUIPMENT GROUND PER 250-122. | | | | 4} THE OCP FOR CIRCUIT #5 & 7,IS NOT | | CORRECT FOR #4 WIRE SHOWN FOR THE SUB | | FEED. | | | | 5} PLEASE LIST AND INCLUDE THE SMALL | | APPLIANCE CIRCUITS REQUIRED IN | | 220-16(A),IN THE SCHEDULE AND LOAD | | CALCS. | | | | 6} CIRCUITS #25 & 27IN PANEL "B" FOR THE | | LIVING ROOM SHOW NO LOADS,PLEASE | | CLARIFY. | | | | 7} THE RISER DIAGRAM SHOWS TWO SUB | | PANELS BUT ONLY ONE FEED IS SHOWN AND | | ONLY ONE SUB PANEL SCHEDULE IS | | SHOWN,PLEASE CLARIFY. | | | | IF THERE ARE ANY QEUSTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|