2003-04-30 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE CORRECT THE FOLLOWING AND
 RESUBMIT FOR REVIEW.
  
 1} THE #6 GEC IS INCORRECT FOR THE
 SERVICE SHOWN.MUST BE #2 PER 250-66.
  
 2} THE RISER DIAGRAM SHOWS BOTH SUB
 PANELS COMING FROM PANEL "A",ONLY ONE
 LISTED ON THE THE SCHEDULE.PLEASE
 CLARIFY.
  
 3} THE SUB FEEDERS IN PVC MUST CONTAIN
 AN EQUIPMENT GROUND PER 250-122.
  
 4} THE OCP FOR CIRCUIT #5 & 7,IS NOT
 CORRECT FOR #4 WIRE SHOWN FOR THE SUB
 FEED.
  
 5} PLEASE LIST AND INCLUDE THE SMALL
 APPLIANCE CIRCUITS REQUIRED IN
 220-16(A),IN THE SCHEDULE AND LOAD
 CALCS.
  
 6} CIRCUITS #25 & 27IN PANEL "B" FOR THE
 LIVING ROOM SHOW NO LOADS,PLEASE
 CLARIFY.
  
 7} THE RISER DIAGRAM SHOWS TWO SUB
 PANELS BUT ONLY ONE FEED IS SHOWN AND
 ONLY ONE SUB PANEL SCHEDULE IS
 SHOWN,PLEASE CLARIFY.
  
 IF THERE ARE ANY QEUSTIONS PLEASE CALL.
  