Plan Review Notes
Plan Review Notes For Permit 02021865
Permit Number 02021865
Review Stop R
Sequence Number 1
Notes
Date Text
2002-04-11 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-CLEARLY SPECIFY ON PLANS AREAS TO HAVE
 SAFETY GLASS. SEC. 2405.2 SBC 1997.
 3-PROVIDE ATTIC ACCESS AT MAIN ROOF,
 GARAGE AND 2ND. FL. SEC. 2309.6 SBC/97
 4-SPECIFY SMOKE DETECTORS @ 1ST & 2ND
 FLOOR. SEC. 905.2.2 SBC 1997.
 5-ROOF FRAMING PLAN DOESN'T MATCH EXT.
 ELEVATIONS. REVISE AS REQUIRED.
 6-SEE COMMENTS THROUGHOUT PLANS AND
 REVISE/UPDATE/CLARIFY AS REQUIRED.
 7-PROVIDE COMPLETE DETAILS/SPECS FOR
 POSTS TO RECEIVE ENGINEERED GIRDERS AT
 THE ENDS. SEE COMMENTS ON PLANS.
 8-PROVIDE COMPLETE DETAIL/SPECS FOR 2X
 STRUCTURAL BUCKS AT SWING DOORS AS
 REQUIRED BY PRODUCT APPROVALS.
 9-PROVIDE COMPLETE 2 STORY SECTION/DET.
 AT BONUS ROOM FRONT ELEVATION. SPECIFY
 ALL CONNECTORS. FOUNDATION PLAN, BLDG
 SECTIONS AND EXTERIOR ELEVATIONS ARE
 VERY CONFUSSING AND DON'T MATCH.
 REVISE AS REQUIRED.
 10-PROVIDE STRUCTURAL BUCK DETAIL FOR
 GARAGE DOOR. SEC. 104.2.2 CITY AMENDM.
 AND SEC. 1606 SBC 1997.
 11-PROVIDE COMPLETE SPECS FOR CEILING
 INSTALLATION AT ENTRY AND REAR PORCHES.
 SPECIFY ALL FASTENERS. SEE ASTM C-1063
 12-DESIGN CERTIFICATION FOR BUILDING
 CODE COMPLIANCE FORM IS INCORRECT.
 MEAN ROOF HEIGHT IS 21'-0" +/-, NOT
 17'-0". REVISE VELOCITY PRESSURE
 ACCORDINGLY. SEC. 1606 SBC 1997.
 NOTE: INFORMATION ON THIS FORM TO BE
 INCLUDED ON DWGS. SEPARATE FORM NOT
 REQUIRED.
 13-PROVIDE PRODUCT APPROVAL FOR:
 A)BUTT GLAZING SYSTEM USED. OR COMPLETE
 SITE SPECIFIC ENGINEERING.
 B)ENTRY DOORS WITH LEGIBLE DRAWINGS.
 C)REAR SWING DOOR WITH LEGIBLE DRAWINGS.
 D)GARAGE DOOR THAT WILL RESIST UPLIFT
 LOADS CALCULATED BY ARCHITECT.
 E)FIXED WINDOWS.
 F)WINDOW MULLIONS.
 G)ARCHED WINDOWS.
 H)ROUND WINDOWS.
 I)SLIDING GLASS DOORS
  
 14-STORM PANELS: CLEARLY INDICATE ON
 PLANS MOUNTING SYSTEM AND ANCHOR TYPE
 AND SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 EDGE DISTANCE, PANEL SPAN AND STRUCTURE
 TO BE ATTACHED TO (CONCRETE, CONCRETE
 BLOCK OR WOOD).***NOTE: SEE SHUTTER'S
 SUPPLIER. DWGS CAN'T BE USED. SEE NOTE
 REGARDING DWGS GOOD FOR ONE PERMIT ONLY
 NOTE:PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.