Plan Review Notes
Plan Review Notes For Permit 02021865
Permit Number 02021865
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-14 00:00:00******************UNSAT!****************
  
 PLEASE COMPLY WITH THE FOLLOWING AND
 RESUBMIT FOR REVIEW:
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3} BED ROOM CIRCUITS TO COMPLY WITH
 210-12.
  
 4} INDICATE CONDUCTOR AND WIRE SIZE FOR
 POOL PANEL FEEDER.
  
 5} GIVE LOCATION FOR PANEL "B".
  
 6} PLEASE SHOW LOCATIONS FOR AHU'S AND
 DISCONNECTS.
  
 7} INDICATE LOCATIONS FOR C/U
 DISCONNECTS.
  
 8} THERE ARE HAND DRAWN BOXES AND
 FIXTURES ON THE ELECTRICAL PLAN IN
 VIOLATION OF FS.481-221.
  
 9} THERE ARE NO 2ND FLOOR PLANS ON THE
 ELECTRICAL DRAWING.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392