2002-10-03 00:00:00REVISION DENIED
  
 1) PROVIDE (2) COPIES OF SURVEY WITH THE
 DIMENSIONS OF THE FRONT ENTRY ADDITION
 INDICATED. (ZONING REVIEW IS REQUIRED)
  
 2) THE TRUSS ANCHOR SCHEDULE DOES NOT
 INDICATE THE SIZE OR NUMBER OF NAILS
 REQUIRED FOR THE ATTACHMENT TO THE BEAM,
 FOR ANCHOR A2 (TAPL 16).
  
 3) INDICATE THE MATERIAL THAT WILL BE
 INSTALL ON THE ENTRY CEILING.
  
 4) INDICATE ATTIC VENTS AS REQUIRED BY
 FBC 2309.7.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR ROOFING MATERIAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202