2002-03-06 00:00:00 | |
| NO MECHANICAL PLANS SUBMITTED FOR |
| REVIEW.PLEASE PROVIDE PLANS WITH |
| MECHANICAL PERMIT APPLICATION. |
| |
| PLEASE NOTE, BATHROOM SHALL HAVE A |
| WINDOW WITH A MINIMUM OF 3 SQ FT OF |
| OPEN SPACE OR AIR SHALL BE MECHANICALLY |
| EXHAUSTED. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT 659-8096 |
| EXT. 8388. |
| |
| MECHANICAL PERMIT 00120524 |
| |
| PLEASE PROVIDE MANUFACTURER SUBMITTAL |
| DATA FOR DRYERS BEING INSTALLED IN |
| UNITS THAT THE IN-LINE FAN HAS BEEN |
| DELETED. EXHAUST DUCT EXCEEDS 25FT |
| MAXIMUM AS PER 1997 SMC 509.3. |
| |
| REVISIONS APPROVED WITH THE EXCEPTION |
| OF"PROPOSED KITCHEN HOOD".TERMINATION |
| FOR GREASE DUCT SHALL COMPLY WITH NFPA |
| 96 AND 1997 SMC CHAPTER 5.PLEASE NOTE |
| AS PER 1997 SMC 506.1, TERMINATION OF |
| EXHAUST SHALL BE LOCATED 10 FT FROM ANY |
| ADJACENT BUILDING, PARKING AREA, |
| ADJACENT PROPERTY LINE, WINDOW, DOOR OR |
| AIR INTAKE.ADDITIONAL PLANS & PERMITS |
| REQUIRED FOR HOOD (GREASE DUCT & MAKEUP |
| AIR), FIRE SUPRESSION, AND WALK-IN |
| COOLERS/FREEZERS.PROVIDE MANUFACTURER |
| SUBMITTAL DATA WITH PLANS & PERMIT |
| APPLICATION. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT 659-8096 |
| EXT. 8388. |