Plan Review Notes
Plan Review Notes For Permit 02021861
Permit Number 02021861
Review Stop M
Sequence Number 1
Notes
Date Text
2002-03-06 00:00:00 
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 PLEASE NOTE, BATHROOM SHALL HAVE A
 WINDOW WITH A MINIMUM OF 3 SQ FT OF
 OPEN SPACE OR AIR SHALL BE MECHANICALLY
 EXHAUSTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.
  
 MECHANICAL PERMIT 00120524
  
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 DATA FOR DRYERS BEING INSTALLED IN
 UNITS THAT THE IN-LINE FAN HAS BEEN
 DELETED. EXHAUST DUCT EXCEEDS 25FT
 MAXIMUM AS PER 1997 SMC 509.3.
  
 REVISIONS APPROVED WITH THE EXCEPTION
 OF"PROPOSED KITCHEN HOOD".TERMINATION
 FOR GREASE DUCT SHALL COMPLY WITH NFPA
 96 AND 1997 SMC CHAPTER 5.PLEASE NOTE
 AS PER 1997 SMC 506.1, TERMINATION OF
 EXHAUST SHALL BE LOCATED 10 FT FROM ANY
 ADJACENT BUILDING, PARKING AREA,
 ADJACENT PROPERTY LINE, WINDOW, DOOR OR
 AIR INTAKE.ADDITIONAL PLANS & PERMITS
 REQUIRED FOR HOOD (GREASE DUCT & MAKEUP
 AIR), FIRE SUPRESSION, AND WALK-IN
 COOLERS/FREEZERS.PROVIDE MANUFACTURER
 SUBMITTAL DATA WITH PLANS & PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.