2002-03-13 00:00:00 | DENIED |
| REFERENCE: FBC 2001 |
| |
| 1) FBC SEC 104.2 PLEASE PROVIDE A CLEAR |
| COPY OF POOL LAY OUT SHEET WITH PIPING, |
| DRAIN LAV OUT, RETURNS, ECT. |
| 2) SEC 424.2.6.4 PLEASE SUBMIT MANUFACT- |
| URE RECOMMENDATIONS. |
| 3) SEC 424.2.6.6.2 SUBMIT SPECS. FOR |
| LISTED FITTING FOR VACUUM AND FOR ALL |
| SUCTION INLETS. |
| 4) SEC 424.2.6.6.3 ENTRAPMENT AVOIDANCE, |
| PLEASE SUBMIT DETAILS FOR MAIN DRAIN, |
| AND VACUUM LINE. GIVE INFORMATION ON |
| GRATES AND BACKUP SYSTEMS. |
| 5) SEC 424.2.6.6.5 SHOW DETAILS FOR |
| CLEANER FITTINGS. SHOW LOCATION. |
| 6) SEC 424.2.7.2 SUBMIT DETAILS FOR AN- |
| CHORING EQUIPMENT TO BASE. INDICATE BASE |
| TO BE NOMINAL 4" SLAB. |
| 7) SEC 424.2.9 WATER SUPPLY, LOCAL ORD. |
| #2853-95 BACK FLOW PREVENTER REQUIRED ON |
| WATER SERVICE. PLEASE INDICATE ON NOTES. |
| 8) SEC 424.2.13.2 JOINTS AND CONNECTIONS |
| FBC 2001 PLUMBING SEC 605.21 PURPLE |
| PRIMER REQUIRED ON PVC PIPE AND FITTINGS |
| STATE ON GENERAL NOTES. |
| 9) SEC 424.2.14.2 WATER RETENTION. GIVE |
| DETAILS SHOWING A POSITIVE MEANS OF RE- |
| TAINING WATER IN THE HEATER. SUBMIT MAN- |
| UFACTURE CUT SHEETS SHOWING HOW WATER |
| WILL BE RETAINED. |
| 10) SEC 424.2.14.4 INDICATE THAT ALL |
| WATER HEATER EQUIPMENT TO BE INSTALLED |
| WITH FLANGES OR UNIONS. |
| 11) COMPLY WITH FBC 2001 SEC 104.2 |
| BUILDING DRAWINGS AND SPECIFICATIONS. |
| TOO MANY SWIMMING POOL PIPING SCHEMATICS |
| ON THE PLANS, THIS IS VERY CONFUSING. |
| SHOW INDIVIDUAL PIPING SCHEMATIC FOR EA. |
| SWIMMING POOL. SHOW PIPING FOR THE ENT- |
| IRE SYSTEM, PIPE SIZES, VENTS, SUCTION |
| AND DISCHARGE PIPING ECT. |
| |
| REVIEW BY KEN STEVENS |