Plan Review Notes
Plan Review Notes For Permit 02021852
Permit Number 02021852
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-13 00:00:00DENIED
 REFERENCE: FBC 2001
  
 1) FBC SEC 104.2 PLEASE PROVIDE A CLEAR
 COPY OF POOL LAY OUT SHEET WITH PIPING,
 DRAIN LAV OUT, RETURNS, ECT.
 2) SEC 424.2.6.4 PLEASE SUBMIT MANUFACT-
 URE RECOMMENDATIONS.
 3) SEC 424.2.6.6.2 SUBMIT SPECS. FOR
 LISTED FITTING FOR VACUUM AND FOR ALL
 SUCTION INLETS.
 4) SEC 424.2.6.6.3 ENTRAPMENT AVOIDANCE,
 PLEASE SUBMIT DETAILS FOR MAIN DRAIN,
 AND VACUUM LINE. GIVE INFORMATION ON
 GRATES AND BACKUP SYSTEMS.
 5) SEC 424.2.6.6.5 SHOW DETAILS FOR
 CLEANER FITTINGS. SHOW LOCATION.
 6) SEC 424.2.7.2 SUBMIT DETAILS FOR AN-
 CHORING EQUIPMENT TO BASE. INDICATE BASE
 TO BE NOMINAL 4" SLAB.
 7) SEC 424.2.9 WATER SUPPLY, LOCAL ORD.
 #2853-95 BACK FLOW PREVENTER REQUIRED ON
 WATER SERVICE. PLEASE INDICATE ON NOTES.
 8) SEC 424.2.13.2 JOINTS AND CONNECTIONS
 FBC 2001 PLUMBING SEC 605.21 PURPLE
 PRIMER REQUIRED ON PVC PIPE AND FITTINGS
 STATE ON GENERAL NOTES.
 9) SEC 424.2.14.2 WATER RETENTION. GIVE
 DETAILS SHOWING A POSITIVE MEANS OF RE-
 TAINING WATER IN THE HEATER. SUBMIT MAN-
 UFACTURE CUT SHEETS SHOWING HOW WATER
 WILL BE RETAINED.
 10) SEC 424.2.14.4 INDICATE THAT ALL
 WATER HEATER EQUIPMENT TO BE INSTALLED
 WITH FLANGES OR UNIONS.
 11) COMPLY WITH FBC 2001 SEC 104.2
 BUILDING DRAWINGS AND SPECIFICATIONS.
 TOO MANY SWIMMING POOL PIPING SCHEMATICS
 ON THE PLANS, THIS IS VERY CONFUSING.
 SHOW INDIVIDUAL PIPING SCHEMATIC FOR EA.
 SWIMMING POOL. SHOW PIPING FOR THE ENT-
 IRE SYSTEM, PIPE SIZES, VENTS, SUCTION
 AND DISCHARGE PIPING ECT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377