Plan Review Notes
Plan Review Notes For Permit 02021850
Permit Number 02021850
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-13 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) SEC 424.2.6.4 PLEASE SUBMIT MANUFACT-
 URES RECOMMENDATIONS.
 2) SEC 424.2.6.6.2 SUBMIT SPECS. FOR
 LISTED FITTING FOR VACUMN AND FOR ALL
 SUCTION INLETS.
 3) 424.2.6.6.3 ENTRAPMENT AVOIDANCE,
 PLEASE SUBMIT DETAILS FOR MAIN DRAIN,
 SPA MAIN DRAIN AND VACUMN LINE. GIVE
 INFORMATION ON GRATES AND BACKUP SYSTEM.
 4) SEC 424.2.6.6.5 SHOW DETAILS FOR
 CLEANER FITTINGS. SHOW LOCATION.
 5) SEC 424.2.7.2 SUBMIT DETAIL FOR AN-
 CHORING EQUIPMENT TO BASE. INDICATE BASE
 TO BE NOMINAL 4" SLAB.
 6) SEC 424.2.9 WATER SUPPLY, LOCAL ORD.
 #2853-95 BACK FLOW PREVENTER REQUIRED ON
 WATER SERVICE. PLEASE INDICATE ON NOTES.
 7) SEC 424.2.13.2 JOINTS AND CONNECTIONS
 FBC 2001 PLUMBING SEC 605.21 PURPLE
 PRIMER REQUIRED ON PVC PIPING. STATE ON
 GENERAL NOTES.
 8) SEC 424.2.14.2 WATER RETENTION. GIVE
 DETAILS SHOWING A POSITIVE MEANS OF RE-
 TAINING WATER IN THE HEATER. SUBMIT MAN-
 UFACTURE CUT SHEETS SHOWING HOW WATER
 WILL BE RETAINED.
 9) SEC 424.2.14.4 INDICATE THAT ALL
 WATER HEATER EQUIPMENT TO BE INSTALLED
 WITH FLANGES OR UNIONS.
 10) SEC 424.2.15 GAS PIPING, SEPARATE
 PLANS AND PERMIT REQUIRED
 11) COMPLY WITH FBC 2001 SEC 104.2
 BUILDING DRAWINGS AND SPECIFICATIONS
 TOO MANY SWIMMING POOL PIPING SCHEMATICS
 ON THE PLAN, THIS IS VERY CONFUSING.
 SHOW INDIVIDUAL PIPING SHCEMATIC FOR EA.
 SWIMMING POOL, SPA. SHOW PIPING FOR THE
 ENTIRE SYSTEM, PIPE SIZES, VENTS, SUCT-
 ION AND DISCHARGE PIPING ECT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377