Plan Review Notes For Permit 02021837 |
Permit Number |
02021837 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-04-02 00:00:00 | DENIED; | | 1.WATER HEATER SHALL BE READLY ACCESS- | | ABLE PER 94 SPC SEC. 501.7. INSTALL | | WATER HEATER ON FLOOR OR OTHER READLY | | ACCESSABLE LOCATION. | | 2.DRINFING FOUNTAIN SHALL ACCOMMODATE | | PEOPLE WHO HAVE DIFFICULTY BENDING AND | | PEOPLE IN WHEEL CHAIRS. SEE 97 FACBC | | SEC 4.1.3 (10). | | 3.APPROVED ENGINEERED MECHANICAL HAMMER | | ARRESTERS SHALL BE SIZED BY THE | | ENGINEER AND INSTALLED PER MANUFACTORS | | RECOMENDATIONS. SEC 607.8.2. PAGE P-1 | | WATER RISER DIAGRAM, DELLETE AIR | | CHAMBER FROM DRAWING AND SHOW LOCATION | | OF REQUITED MHA'S. | | 4.PAGE P-1 DRY WELL DETAIL. INSTALL A | | TEE IN CONDENSATE PIPE BEFORE THE | | DRY WELL EXTEND TEE ABOVE GROUND AND | | PUT A "U' BEND ONPIPE. THIS SERVICE | | AS A VENT AND AN OVERFLOW OUTLET. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT 8369 |
|