2002-04-02 00:00:00DENIED;
 1.WATER HEATER SHALL BE READLY ACCESS-
 ABLE PER 94 SPC SEC. 501.7. INSTALL
 WATER HEATER ON FLOOR OR OTHER READLY
 ACCESSABLE LOCATION.
 2.DRINFING FOUNTAIN SHALL ACCOMMODATE
 PEOPLE WHO HAVE DIFFICULTY BENDING AND
 PEOPLE IN WHEEL CHAIRS. SEE 97 FACBC
 SEC 4.1.3 (10).
 3.APPROVED ENGINEERED MECHANICAL HAMMER
 ARRESTERS SHALL BE SIZED BY THE
 ENGINEER AND INSTALLED PER MANUFACTORS
 RECOMENDATIONS. SEC 607.8.2. PAGE P-1
 WATER RISER DIAGRAM, DELLETE AIR
 CHAMBER FROM DRAWING AND SHOW LOCATION
 OF REQUITED MHA'S.
 4.PAGE P-1 DRY WELL DETAIL. INSTALL A
 TEE IN CONDENSATE PIPE BEFORE THE
 DRY WELL EXTEND TEE ABOVE GROUND AND
 PUT A "U' BEND ONPIPE. THIS SERVICE
 AS A VENT AND AN OVERFLOW OUTLET.