Plan Review Notes
Plan Review Notes For Permit 02021837
Permit Number 02021837
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-03-26 00:00:00A) BUILDING ADDRESS REQUIRED.
 B) WRONG LIFE SAFETY CODE REFERENCED
 ON PLANS. SHOULD READ THE FLORIDA
 FIRE PREVENTION CODE, 2000 EDITION OF
 THE LIFE SAFETY CODE.
 C) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 D) STORAGE ROOM 117,AND
 STORAGE/MECHANICAL ROOM 104 ARE TO BE
 AT LEAST ONE HOUR FIRE RATED AND BE
 EQUIPPED WITH AT LEAST C LABELED FIRE
 DOORS, SINCE NO FIRE SPRINKLERS ARE
 PLANNED.
 E) DOOR 122 FOR THE JANITOR'S ROOM
 IS NOT FIRE RATED LIKE THE ROOM IS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910