Plan Review Notes For Permit 02021837 |
Permit Number |
02021837 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-03-14 00:00:00 | ******************* UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE, THAT PER LOCAL | | AMENDMENTS.230-70A. NO MORETHAN 8' OF | | UNPROTECTED CONDUCTORS INSIDE THE BLDG. | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | PLEASE SEE NEC 220-3,220-10,220-11, | | 220-13 AND ALL CONTINUOUS LOADS PER | | 230-42,215-2,3. | | | | 3)NOTE: PLEASE SEE 230-76, 230-79 FOR | | MANUAL MEANS OF DISC AND RATING OF | | SERVICE MAIN TO CLARIFY SHUNT TRIP. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | PLEASE SEE FIRE REVIEW FOR ANY COMMENTS | | THAT MAY AFFECT ELECTRICAL PLANS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|