Plan Review Notes
Plan Review Notes For Permit 02021837
Permit Number 02021837
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-14 00:00:00******************* UNSAT **************
  
  
 1)NOTE: PLEASE NOTE, THAT PER LOCAL
 AMENDMENTS.230-70A. NO MORETHAN 8' OF
 UNPROTECTED CONDUCTORS INSIDE THE BLDG.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SEE NEC 220-3,220-10,220-11,
 220-13 AND ALL CONTINUOUS LOADS PER
 230-42,215-2,3.
  
 3)NOTE: PLEASE SEE 230-76, 230-79 FOR
 MANUAL MEANS OF DISC AND RATING OF
 SERVICE MAIN TO CLARIFY SHUNT TRIP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLEASE SEE FIRE REVIEW FOR ANY COMMENTS
 THAT MAY AFFECT ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372