2002-03-04 00:00:00 | PROVIDE A DETAIL FOR CUTTING THE SECOND | | FLOOR, AND THE ROOF.ALSO, SHOW THE | | FIRE RATED SHAFT REQUIRED BY SBC 705.6. | | INCLUDE PENETRATIONS FOR THE ELECTRICAL. | | | | WILL THE DEMISING WALL BE CONSTRUCTED | | COMPLETELY?PLANS SHOW DRY WALL TO BE | | INSTALLED AT A LATER DATE. | | | | SHOW THE MEANS OF EGRESS FROM THE NEWLY | | DEMISED SPACES SHOWN AS R1 AND R1A. | | | | IF THE NEW DOOR ON THE NORTH END OF | | SPACE R1A DISCHARGES TO AN EXIT COURT | | OR SIMILAR, THAN THE LOUVER ABOVE MUST | | BE FIRE PROTECTED AS WELL.SEE SBC | | 1010.2 & SBC 1010.3. |
|