Plan Review Notes
Plan Review Notes For Permit 02021826
Permit Number 02021826
Review Stop B
Sequence Number 1
Notes
Date Text
2002-04-29 00:00:00CHECKLIST:
 1-BRING DRAWINGS TO PALM BEACH COUNTY TO
 PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 2-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 SBC 1997.
 3-REVISE ROOF SLOPE. MIN. SLOPE TO BE
 1/4" PER FT. SEC. 1503.1.2.3 SBC 1997.
 4-ENGINEER TO SPECIFY ON PLANS HOW IS
 NEW FOUNDATION AND WALL GOING TO BE
 ATTACHED TO EXISTING FOUNDATION AND
 WALLS. SEC. 104.2.2 CITY AMENDMENTS TO
 SBC 1997.
 5-PROVIDE COMPLETE WALL SECTION/DETAIL
 THRU EXISTING WALL AND NEW ROOF.
 SPECIFY HOW NEW 4X6 ROOF JOISTS ARE
 GOING TO BE ANCHORED USING SIMPSON OR
 USP CONNECTOR SPECIFIED ON ROOF
 FRAMING PLAN. NOTE: THIS CONNECTOR IS
 DESIGNED TO BE EMBEDDED INTO CONCRETE.
 HOW IS THE CONNECTOR GOING TO BE
 EMBEDDED INTO EXISTING CONCRETE BEAM?
 6-CLARIFY WHICH TYPE OF CONCRETE SLAB IS
 GOING TO BE USED. WALL SECTION CALLS
 FOR WIRE MESH WHILE FOUNDATION PLAN
 CALLS FOR FIBER MESH.
 7-PROVIDE PRODUCT APPROVAL FOR:
 A)FLAT ROOF SYSTEM SPECIFIED ON PLANS.
 B)SINGLE HUNG WINDOWS WINDOWSWITH
 APPROVED DRAWINGS.
 C)EXTERIOR DOOR WITH APPROVED DRAWINGS.
 D)STORM SHUTTERS WITH APPROVED DRAWINGS.
 SPECIFY SYSTEM AND ANCHOR TYPE AND
 SPACING TO BE USED.
 8-OWES $83.04 FOR UPDATED VALUATION AND
 RADON FEES.
 9-ENGINEER SPECIFY THE DESIGN PRESSURES
 CALCULATED FOR EXTERIOR OPENINGS PER
 SECTION 1606 SBC 1997.