Plan Review Notes For Permit 02021748 |
Permit Number |
02021748 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-04-12 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | 1) COMPLY WITH FBC-2001 SEC 424.2 | | PRIVATE SWIMMING POOLS. | | 2) FBC-2001 SEC 424.2.6.1 ENGINEERING | | DESIGN, CONSTRUCTION AND WORKMANSHIP. | | ANSI/NSPI-4 92. | | 3) | | FBC-2001 SEC 424.2.6.6.5 WHERE PROVIDED, | | THE VACUUM OR PRESSURE CLEANER FITTING | | SHALL BE LOCATED AT LEAST 6" AND NOT | | GREATER THAN 12" BELOW THE MINIMUM OPER- | | ATING WATER LEVEL OR AS AN ATTACHMENT TO | | THE SKIMMER. | | 4) VALVES REQUIRED FOR HEATER BYPASS | | 5) | | FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL | | ORD. #2853-95, BACKFLOW REQUIRED ON | | WATER SERVICE. (ADD TO NOTES) | | 6) | | FBC-2001 SEC 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | 7) | | FBC-2001 SEC 424.2.13.2JOINTS AND CON- | | NECTIONS, FBC PLMG SEC 605.21, PURPLE | | PRIMER REQUIRED ON PVC PIPING. (ADD TO | | NOTES) | | 8) | | FBC-2001 SEC 424.2.15 GAS PIPING SHALL | | COMPLY WITH FBC FUEL GAS. SEPARATE PLANS | | AND PERMIT REQUIRED. | | 9) SIGNED AND SEALED PLANS SHALL NOT | | HAVE CHANGES PENNED ON PLANS. NEW SIGNED | | AND SEALED PLANS SHALL BE RESUBMITTED. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|