2002-03-07 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THERE IS NOT ENOUGH | | INFORMATION SHOWN FOR WHERE ELECTRICAL | | IS BEING FED FROM. 215-5 | | PLEASE PROVIDE LOAD CALCS | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S) PER 210-11-C-3. | | MUST BE 20A AND #12AWG. | | | | 3)NOTE: PLEASE NOTE A SMOKE DETECTOR IS | | REQ`D UPSTAIRS. NFPA-72 2-2.1.1.1. | | | | 4)NOTE: PLEASE NOTE ALL OUTLETS IN | | GARGAGE ARE TO BE SHOWN AS GFI/GFI | | PROTECTED. 210-8 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|