Plan Review Notes
Plan Review Notes For Permit 02021697
Permit Number 02021697
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-07 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THERE IS NOT ENOUGH
 INFORMATION SHOWN FOR WHERE ELECTRICAL
 IS BEING FED FROM. 215-5
 PLEASE PROVIDE LOAD CALCS
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3)NOTE: PLEASE NOTE A SMOKE DETECTOR IS
 REQ`D UPSTAIRS. NFPA-72 2-2.1.1.1.
  
 4)NOTE: PLEASE NOTE ALL OUTLETS IN
 GARGAGE ARE TO BE SHOWN AS GFI/GFI
 PROTECTED. 210-8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372