Plan Review Notes
Plan Review Notes For Permit 02021697
Permit Number 02021697
Review Stop B
Sequence Number 1
Notes
Date Text
2002-03-13 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02021697
 1219 FLORIDA AV
 CONT: KEITH TURNEY
 TEL: 684-0905
  
 SBC= 1997 STANDARD BUILDING CODE
 FLBC= 2001 FLORIDA BUILDING CODE
  
 1)- PLANS SUBMITTED BETWEEN JAN.1, 2002
 AND FEB. 28, 2002 SHALL INDICATE AS TO
 WHICH CODE THEY ARE DESIGNED TOO? THIS
 REVIEW SHALL BE COMPLETED UNDER THE
 1997 SBC.
  
 2) PLANS INDICATE A WINDOW DRAWN IN ON
 THE EAST SIDE, NOT AS PART OF THE ARCH.
 ORIGINAL DEPICTION, ARCH. TO REVIEW AND
 OK BY LETTER FORM SIGN & SEAL. TO BE APP
 ROVED BY HISTORICS BEFORE PLANS ARE ISSU
 ED.
  
 3)- THE PLANS DO NOT INDICATE DESIGN
 PARAMETERS & ASSUMPTIONS AS REQUIRED
 BY CHAPTER 16, FL. ST. S 481 & 553.
  
 4)- THE PLANS & PERMIT APPLICATION IN-
 DICATE THAT THE NORTH & WEST WALLS ARE
 TO REPLACED AS WELL AS THE CONCRETE SLAB
 SBC 1804.1.3 THE BOTTOM OF THE FOOTER
 SHALL BE 12" BELOW GRADE. THE SUB-SHEATH
 ING REQUIRES A CLEARENCE OF 6" BETWEEN
 THE EARTH AND SHEATHING UNLESS SHEATHING
 AND FRAMING ARE OF APPROVED PRESERVATIVE
 TREATED WOOD OR APPROVED NATURALLY
 DURABLE WOOD.
  
 5)- SBC 1606.2.5.2 THE PRESSURE ZONES
 ARE TO BE INDENTIFIED ON THE PLANS, POSI
 TIVE & NEGITIVE PRESSURES FOR ALL OPEN-
 INGS.
  
 6)- THE PRODUCT APPROVAL SUBMITTAL FORM
 FOR THE GARAGE DOOR IS TO BE REJECTED
 WITHOUT CALCULATIONS INDICATING THAT
 THE DOOR AND HARDWARE MEET THE WIND
 REQUIREMENTS OF CHAPTTER 16.
  
 7)- SBC TABLE 600 FOR TYPE VI STRUCTURES
 LESS THAN 3'-0" FROM THE PROPERTY LINE
 A 1 HR RATING IS REQUIRED FOR THE EXTER-
 IOR WALL, INDICATE CODE COMPLIANCE
 SBC 709.6.2.2.
  
 8)- SBC 1007.3.1 TREADS & RISERS 2R+1T=
 24TO 25".
  
 9)- SBC 1203.4.2 EVERY TOLIET ROOM SHALL
 HAVE A WINDOW OR MECHANICAL VENTILATION.
  
 10)- PLANS DO NOT INDICATE ANY HURRI-
 CANE STRAPPING FROM RAFTER TO RAFTER
 AT THE RIDGE.
  
 11)- PRODUCT TESTING REPORTS, THE STEEL
 SIDE DOOR REPORT EXPIRED, MISSING REPORT
 FOR ROOFING MATERIALS.
  
 12)- CONTRACTOR TO SSUBMIT PLANS TO THE
 COUNTY FOR IMPACT FEE ASSESSMENT.
  
 13)- THE PERMIT VALUE OF $19,000.00 IS
 LOW. THE AVERAGE FOR TYPE VI CONST IS
 49.92 X 900= 45,000 WITHOUT VALUE TO
 THE 900 SQ FT TO THE FIRST FLOOR.
  
 14)- HOLD ON PROPERTY, 4X FEE BLDG W/O
 FENCE PERMIT, 01/24/01 BOB COMPTON.
  
 15)- TO PAY ADDTIONAL RADON FEES.