Plan Review Notes
Plan Review Notes For Permit 02021514
Permit Number 02021514
Review Stop FS
Sequence Number 2
Notes
Date Text
2002-03-08 00:00:00A) ACCORDING TO NFPA 13, 1999 EDITION,
 SECTION 5-13.6.1 "SIDEWALL SPRAY
 SPRINKLERS SHALL BE INSTALLED AT THE
 BOTTOM OF EACH ELEVATOR HOISTWAY NOT
 MORE THAN 2 FEET ABOVE THE FLOOR OF THE
 PIT". THE ONLY EXCEPTION TO THIS IS IF
 THE ELEVATOR SHAFT DOES NOT CONTAIN
 COMBUSTIBLE HYDRAULIC FLUIDS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910