Plan Review Notes For Permit 02021514 |
Permit Number |
02021514 |
|
Review Stop |
FS |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-03-08 00:00:00 | A) ACCORDING TO NFPA 13, 1999 EDITION, | | SECTION 5-13.6.1 "SIDEWALL SPRAY | | SPRINKLERS SHALL BE INSTALLED AT THE | | BOTTOM OF EACH ELEVATOR HOISTWAY NOT | | MORE THAN 2 FEET ABOVE THE FLOOR OF THE | | PIT". THE ONLY EXCEPTION TO THIS IS IF | | THE ELEVATOR SHAFT DOES NOT CONTAIN | | COMBUSTIBLE HYDRAULIC FLUIDS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|