2002-04-20 00:00:00 | DENIED |
| REFERENCE: SPC-94 - SGC-97 - FACBC-97 |
| |
| 1) FROM PREVIOUS REVIEW (#2) PLEASE SHOW |
| ON PLANS APPROVED AIR CHAMBERS, (SEE |
| ATTACHED SHEET). AIR CHAMBERS SHALL BE |
| RECHARGEABLE AND ACCESSIBLE PER SPC SEC |
| 607.8.3SHT P-5.1 |
| 2) FROM PREVIOUS REVIEW. SHT P5.1 WATER |
| ISOMETRIC, DOUBLE LAVS AND DRINKING |
| FOUNTAIN (3 FIXTURES) ARE BEING SUPPLIED |
| WITH 1/2" COLD. MAXIMUM FIXTURES SUPPLI- |
| ED WITH 1/2" COLD IS 2 FIXTURES. MODEL |
| COUNTYWIDE AMENDMENTS TO THE SPC-94 SEC |
| 607.7. THIS HAS NOT BEEN CHANGED. |
| 3) FOLLOWING GAS PERMIT APPLICATION REQ- |
| UIREMENTS HAVE NOT BEEN ADDRESSED. |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER STANDARD |
| GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| C. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER STANDARD GAS CODE SEC. 305.2. IF |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| STANDARD GAS CODE SEC. 402. |
| E. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. SHOW THIS |
| ON GAS RISER DIAGRAM |
| F. SHT P5.1 GAS PIPING ISOMETRIC, TRENCH |
| W/OPEN GRATE STILL SHOWN ON PLAN. INDIC- |
| ATE ON PLAN THAT PIPE WILL BE PAINTED |
| WITH A BITUMASTIC PAINT AND FILL TRENCH |
| WITH A LIGHT WEIGHT CONCRETE TO ALLOW |
| FOR EASY REMOVAL AND SERVICE OF PIPE. |
| |
| REVIEW BY KEN STEVENS |