Plan Review Notes
Plan Review Notes For Permit 02021392
Permit Number 02021392
Review Stop P
Sequence Number 1
Notes
Date Text
2002-02-26 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A6 DETAIL 1/A6 URNAL IN MENS ROOM
 STATES HC WATER CLOSET. PLEASE SHOW
 CLEAR FLOOR SPACE FOR ALL HDCP FIXTURES.
 2) SHTS P0.1/P5.1 DOMESTIC WATER ISO.
 SHOWS AIR CHAMBERS AT TOP OF DROPS, AND
 PLUMBING NOTES #13 STATES WATER HAMMER
 ARRESTORS TO BE USED. PLEASE CLARIFY. IF
 WATER HAMMER ARRESTORS ARE TO BE USED,
 THEY SHALL BE LOCATED NEAR FIXTURE NOT
 AT TOP OF DROP.
 3) SHT P5.1 WATER ISO. DOUBLE LAVS AND
 DRINKING FOUNTAIN (3 FIXTURES) ARE BEING
 SUPPLIED WITH 1/2" COLD. MAXIMUM FIXTUR-
 ES SUPPLIED BY 1/2" COLD IS 2 FIXTURES.
 MODEL COUNTYWIDE AMENDMENTS TO THE SPC-
 94 SEC 607.7
 4) SHT P5.1 SEPARATE GAS PERMIT REQUIRED
 SEE FOLLOWING LIST OF PERMIT APPLICA-
 TION REQUIREMENTS. PROVIDE INFORMAT-
 ION REQUESTED.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 5) SHT P5.1 GAS PIPING ISOMETRIC, TRENCH
 W/OPEN GRATE NOT APPROVED. SEE SGC-97
 SEC 308.4.2(2) CHANNEL TO BE SUITABLY
 COVERED SO AS TO PREVENT THE ENTRANCE OF
 CORROSIVE MATERIALS. PAINTING PIPE WITH
 A BITUMASTIC PAINT AND FILL TRENCH WITH
 LIGHT WEIGHT CONCRETE TO ALLOW FOR EASY
 REMOVAL AND SERVICE OF PIPE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377