Plan Review Notes
Plan Review Notes For Permit 02021392
Permit Number 02021392
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-02-22 00:00:00A) WHAT TYPE OF COOKING WILL BE
 PERFORMED AT THIS LOCATION. IT WAS
 NOTED THAT HOOD,DUCT,AND EXTINGUISHING
 SYSTEMS ARE PLANNED. WILL THE FOOD BE
 SOLD OR SAMPLED ON SITE. SEPARATE
 PLANS AND PERMITS WILL BE REQUIRED FOR
 ANY HOOD,DUCTS,OR EXTINGUISHING SYSTEMS.
 B) NO FIRE SPRINKLER DRAWINGS
 PROVIDED WITH PLANS.
 C) MANUAL PULL STATIONS ARE NOT
 REQUIRED IN MERCANTILE OCCUPANCIES.
 D) THE FIRE ALARM NOTES SECTION
 INDICATES CLASS B, STYLE C. ONLY CLASS
 A, STYLE D CIRCUITS WILL BE PERMITTED.
 E) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM EQUIPMENT.
 F) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR THE
 WALLS AND CEILINGS OF THE SPACE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910