Plan Review Notes For Permit 02021392 |
Permit Number |
02021392 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-02-22 00:00:00 | A) WHAT TYPE OF COOKING WILL BE | | PERFORMED AT THIS LOCATION. IT WAS | | NOTED THAT HOOD,DUCT,AND EXTINGUISHING | | SYSTEMS ARE PLANNED. WILL THE FOOD BE | | SOLD OR SAMPLED ON SITE. SEPARATE | | PLANS AND PERMITS WILL BE REQUIRED FOR | | ANY HOOD,DUCTS,OR EXTINGUISHING SYSTEMS. | | B) NO FIRE SPRINKLER DRAWINGS | | PROVIDED WITH PLANS. | | C) MANUAL PULL STATIONS ARE NOT | | REQUIRED IN MERCANTILE OCCUPANCIES. | | D) THE FIRE ALARM NOTES SECTION | | INDICATES CLASS B, STYLE C. ONLY CLASS | | A, STYLE D CIRCUITS WILL BE PERMITTED. | | E) SEPARATE PLANS AND PERMITS REQUIRED | | FOR FIRE ALARM EQUIPMENT. | | F) PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR THE | | WALLS AND CEILINGS OF THE SPACE. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|