2002-03-01 00:00:00****************** UNSAT ************
  
 1)NOTE: PLEASE CLARIFY LOADS SHOWN FOR
 SOME RECEPT CIRCUITS ARE AT 180VA PER
 OUTLET. PLEASE NOTE SOME DO NOT SHOW
 THE SAME AMOUNT/ PLEASE DOUBLE CHECK
 LOADS FOR OUTLETS SHOWN. PLEASE SEE
 220-3/220-10/220-11/220-13
 LOAD WATTS PER SQ FT ETC.
 PLEASE NOTE THAT IT HAS BEEN COMMON TO
 SHOW CONNECTED LOADS. WE STILL NEED TO
 SEE THE CALCS.
  
 2)NOTE: PLEASE SHOW LOADS FOR TRACK
 LIGHTING PER 220-12B.
  
  
 PLEASE SUBMIT THE ABOVE INFORAMTION FOR
 REVEIW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  