Plan Review Notes
Plan Review Notes For Permit 02021234
Permit Number 02021234
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-04 00:00:00PLUMBING PLAN REVIEW, FBC 2001,DENIED.
 (1) GENERAL NOTES #1 THE CURRENT CODE
 IS FBC 2001,SEC 424.2.6 ENGINEERING
 DESIGN.NOT SBCCI-94 PBC SWIMMING POOL
 (2) NOTE #5 DISPOSAL OF WATER. SEE FBC
 2001,SEC 424.2.10 WASTE WATER DISPOSAL.
 (3) NOTE #7 WATER SUPPLY.SEE FBC 2001
 SEC 424.2.9 WATER SUPPLY. AND LOCAL ORD
 #2853-95 BACK FLOW PREVENTER REQUIRED
 ON WATER SERVICE.
 (4) POOL,SPA SCHEMAIC NOT APPROVED.
 SPA MAIN DRAIN NOT SHOWN ON SCHEMATIC.
 SWIMMING POOL HEATER, SEC 424.2.14 WATER
 HEATING EQUIPMENT. WATER RETENTION PROVI
 DE A DETAIL OF A POSITIVE MEANS OF RETAI
 NING WATER IN THE POOL HEATER WITH A
 BY-PASS.
 (5) FL ENERGY CODE SEC 612.1ABC 2.3.2
 SPAS, HEATED POOLS SHALL BE EQUIPED WITH
 A COVER TO MINIMIZE HEAT LOSS.
 (6) SEC 424.2.15 GAS PIPING, SEPERATE
 PLANS AND PERMIT REQUIRED.
 (7) SEC 424.2.13.2 JOINTS, CONNECTIONS.
 PURPLE PRIMER REQUIRED ON PVC PIPING,
 FBC 2001 PLUMBING, SEC 605.21
 (8)424.2.7.2 PROVIDE DETAILS OF MOUNTING
 AND ANCHORING POOL EQUIPMENT.
 (9) SEC 424.2.6.6.2 SUCTIONS FITTINGS.
 PROVIDE A DETAIL OF VACUM CLEANING INLET
 END OF COMMENTSPAUL SCHMITZ